4.3.5.11 Recording conguration
Recordingconguration
• Upto16recordscanbeconguredwhenconguringrecording.
• A record can have a maximum of 1000 values.
• A record holds a measurement value or the mean value of the measurement value.
• Mean value records can also include the minimum and the maximum values.
• Mean values, minimum values and maximum values are derived from the measurement values in the
measurement timeframe.
• The mean value measurement timeframe is established by the time set under “Time basis”.
• Measurement values are saved once the time set under “Time basis” has run its course (Calculating re-
quired memory capacity).
Settingup/editingarecordingconguration
• An individual recording instance can be set up using the New or Edit buttons.
• Measurement values are selected in the recording window using the Add values button.
• Todosodragthedesiredmeasurementvalue(measurementvaluegroup)overthevalueeld.The
measurement values are adopted and displayed.
• The selected measurement values can be described in more detail via the option “Mean (arithmetical)”,
“Mean (RMS)”, “Minimum”, “Maximum”, “Sample” and “With value change”.
- Mean (arithmetical)
The arithmetical mean is the ratio of the sum and the number of all 200 ms measurement values:
x(arithm.) = (x1+x2+x3...) / n
- Mean (rms)
This value describes a quadratic mean (potential mean) with: x (rms) = root ((x12+x22+x32+..) / n)
- Minimum / Maximum
When these buttons are selected, the means of the minimum and/or maximum values are recorded.
- Sample
Sampledescribestherecordingofthemeasurementvaluewithinthedenedtimeduration.Thetime
baselinedenesthetimeintervalsatwhichtherecordingismade.
• With value change
If the measurement value is changed, the 200 ms measurement value is recorded. This setting is useful
for, for example, the monitoring of digital inputs and outputs (not with high frequency signals) or of the
temperature input.
In contrast to the arithmetical mean, the quadratic mean is of increasing importance when the measurement
valuesvarygreatlycyclically.Outliersinthemeasurementvaluesthushaveagreatersignicance.Witha
value like voltage, it is a good idea to take this more into account than for a power value.
• Using the Delete values button, selected measurement values can be deleted.
EN 50160 and EN 61000-2-4 presettings selection aid
• ViatheEN50160andEN61000-2-4buttons,recordingcongurationscanbepredened.
• If the device does not support measurement as per EN 50160, a prompt appears.