3.4.11 Example: Deleting work
Deleting the effective and the apparent consumption metersusing the time switch.
The “Reset” function provides the following selections, for example for a Energy Analyser D550:
• Resetting all effective and apparent consumption meters.
• Resetting all reactive consumption meters.
• Resetting all minimum and maximum values.
• Resetting the measurement period for EMAX.
3.4.12 Example: Sending e-mail
Sending an email in the event of an undervoltage of < 200 V in phases L1, L2 or L3.
Recipient’s address: martin.musterman@server.de
Sender address: energymeter750@gmx.de
Additional information: Voltage values from the 3 phases at the time of the undervoltage
• Create the Jasic program as shown in below graphic (see Jasic start).
- Required components provided in the Palette window:
- Repeater, group, system variables, constants (numeric), comparator above the threshold value,
BooleanORlinks4xOn,anktriggersequencecontrolandemailoutbox.
- Assign the respective voltages to the system variables and assign desired value to the constants (in
this case 200 V).
- Establish the connections between the components.
- Openthe“Sendemail”modulebydouble-clickingandcongurethiswith:
- informationaboutyouroutgoingmailserver(server,authenticationmode,userandpassword).Ask
your administrator about this!
- with the recipient’s e-mail
- with the sender address, the subject line and the content of the respective e-mail.
- Using the “Add measurement values” button, select the voltages L1, L2 and L3 for the email attach-
ment.
- Dragtheselectedmeasurementvaluestotheemailmessageseld.
- You can now insert further text in the message.
• Save the program on the Energy Analyser D550 via the button “Transmit” or “Transmit to...”.
• Savetheprogramwith“Saveas”asaJasictemplateor“Saveunder”asaleonyourcomputer.
NOTE: Information about your outgoing mail server and the authentication mode can be obtained from your