Approval/Certificate/Document of Conformity

BS EN 45545-2:2013+A1:2015
Executive Summary
Objective
To determine the optical density produced from the following product when tested
in accordance with method T10.03 as defined in BS EN 45545-2: 2013+A1:2015
at an irradiance level of 25kW/m
2
with a pilot flame.
Generic Description
Product reference
Thickness
Density
Crosslinked ethylene vinyl
acetate (EVA) heat shrink tubing
“HSS-HF & “HS-HF”
0.4-1mm
1.4g/ml³
Please see page 5 of this test report for the full description of the product tested
Test Sponsor
Weidmüller Interface GmbH & Co. KG, Klingenbergstraße 16, 32758 Detmold,
Germany
Summary of Test
Results:
The average Ds(max) value determined within 10 minutes was 92
Date of Test
26
th
& 27
th
May 2016
This test report is additional to that issued as 364995 dated the 31
st
May 2016 and has been issued at the
request of the sponsor. The original test report remains valid and is not replaced by this additional test report.
The product referred to in the original report and this additional test report has not been re-tested since the
original test and neither has a technical review of the original test report resulting in any technical changes
been carried out.
The original product reference of the product has been removed and the reference “HSS-HF” & “HS-HF” has
been inserted and the original sponsor name and address details have been removed and those of Weidmüller
Interface GmbH & Co. KG” have been inserted. The sponsor of the test has stated that the material described in
this additional report is identical to the material which was tested. Both the original and the alternative trade
names of the product and the original and alternative sponsor details have been documented and the
documentation is maintained in the confidential file covering this investigation.
Signatories
Responsible Officer
T. Mort *
Senior Technical Officer
Authorised
S. Deeming *
Business Unit Head
* For and on behalf of Exova Warringtonfire.
Report Issued: 28
th
July 2017
This version of the report has been produced from a .pdf format electronic file that has been provided
by Exova Warringtonfire to the sponsor of the report and must only be reproduced in full. Extracts or
abridgements of reports must not be published without permission of Exova Warringtonfire.
Document No.: Additional Test Report
386710
Page No.: 2 of 10
Author: T. Mort Issue Date: 28
th
July 2017
Client: Weidmüller Interface
GmbH & Co. KG
Issue No.: 1