Approval/Certificate/Document of Conformity

NF X 70100-1: 2006 & NF X 70-100-2: 2006
Test Results
Applicability of
test results
The test results relate only to the behaviour of the specimens of the product
under the particular conditions of test; they are not intended to the sole criterion
for assessing the potential smoke hazard of the product in use.
The test results relate only to the specimens of the product in the form in which
they were tested. Small differences in the composition of the product may
significantly affect the performance during the test
and will therefore invalidate
the test results. It is the responsibility of the supplier of the product to ensure
that the product, which is supplied, is identical with the specimens, which were
tested.
Expression of
Gas Content
C C.I.T. calculation as described in NF F 16-101 (withdrawn)
The contents "ti" of gases (CO, CO
2
, HCl, HBr, HF, HCN and SO
2
) are expressed
in milligrams of gas per gram of material. From these values of "ti", and the
corresponding reference values "cc
l
", a conventional index of toxicity, designated
"C.I.T", is determined using the following equation:-
C.I.T = 100 x
ti
cc
l
R value calculation as described in BS 6853 Annex B.1 (withdrawn)
The contents of gases (CO, CO
2
, HCl, HBr, HF, SO
2
, HCN, NO
2
) are expressed in
milligrams of
gas per gram of material. From these values of “cx” and the
corresponding values of reference values “fx”, a weighted summation of toxicity,
designated "R", is determined using the following equation:-
Rx = cx/fx
R = ∑Rx
C.I.T.
NLP
calculation as described in (BS EN 45545-2:2013+A1:2015)
The contents "c
i
" of gases (CO, CO
2
, HCN, HCl, HBr, HF, SO
2
and NO
x
) are
expressed in milligrams of gas per gram of material. From these values of “c
i
” and
the corresponding values of reference values “C
i
”, a conventional index of toxicity,
designated "C.I.T", is determined using the following equation:-
C
c
i
i
= C.I.T
Note, NF F 16-101 (withdrawn), BS 6853 (withdrawn) and (BS EN 45545-
2:2013+A1:2015) utilised different reference values
The individual results obtained are given in table 1.
Document No.: Additional Test Report
386712
Page No.: 7 of 11
Author: T. Mort Issue Date: 28
th
July 2017
Client: Weidmüller Interface
GmbH & Co. KG
Issue No.: 1