User Documentation

Planning
2053260000/05/2015
33
When installing the shielding connection, observe the following:
Remove the sheath of the PROFINET cable only to the
extent required for the connection. The PROFINET cable
is sensitive to mechanical loads in the area where the
sheath was removed.
Make sure you don't damage the shielding when you
strip the sheath off the PROFINET cable.
Do not use the shielding connection as strain-relief.
This would impair the contact between the shielding
and the equipotential bonding. Exception: installation
material specially designed for this purpose.