Planning
Panel feed-throughs and couplings with two sockets are generally
counted as two connector interfaces. The exceptions are panel feed-
throughs and couplings for which the manufacturer has declared in
the manufacturers declaration that these have the performance of a
single socket.
An additional acceptance measurement is also advisable, if such a
measurement is desired for documentation purposes, for PROFINET
cabling. The acceptance procedure should then be conducted as
described in this document.
The requirements in accordance with the PROFINET component standard have
still to be satised, whatever the performance of the acceptance measurement.
In particular, this applies in order to ensure the continued, proper functioning of
the entire system during the entire life cycle of the automation facility, e.g., when
individual PROFINET components are replaced.
(Source:PROFINETCommissioningGuideline,Version1.01,July2010)