3.7.3 Acceptance testers
In certain cases, a simple function measurement with the function tester doesn't
go far enough. A detailed measurement of cabling parameters (e.g. cable
length, attenuation, crosstalk etc.) is needed. Such a measurement can be used
to establish and document numerous cable parameters. After long periods of
cable use, this can be useful if faults arise and the measured values from the
acceptance measurement can be used by way of comparison.
Figure3.4:Extendedacceptancemeasurementonthecabling
In line with the applicable standards, the cable's plug-in connector is not normally
included in the measurement. If plug-in connectors can be assembled on-site, the
connectors and their contacts should be included in the measurement.
Note that with this measurement procedure, special measurement cords or
adapters may have to be used so that the results aren't affected.