Approval/Certificate/Document of Conformity

[13]
Schedule
[14] TYPE EXAMINATION CERTIFICATE No.
DEMKO 18 ATEX 2045X Rev. 0
00-IC-F0060-1 – Issue 14.0
This certificate may only be reproduced in its entirety and without any change, schedule included. Page 2 of 2
[15] Description of Equipment:
Models IE-WL-VL-AP-BR-CL-US, IE-WL-VL-AP-BR-CL-EU, IE-WLT-VL-AP-BR-CL-US, IE-WLT-VL-AP-BR-CL-EU is Industrial Wireless
Access Point
that are evaluated as open-type devices. They are indented for installation into an ultimate enclosure and can be installed
either by DIN-Rail mounting or Wall mounting. The ultimate enclosure must be use a tool removable door or cover.
The subject devices
can be powered through a power supply terminal block or Power Over Ethernet (PoE).
Temperature range:
The relation between ambient temperature and the assigned temperature class is as follows:
Ambient temperature range
Temperature class
-40 °C to +75 °C
T4
Installation instructions:
Conductors rated for a minimum of temperature of 90.1°C must be used for the Power Supply Terminal.
Electrical data
Input: 12-48 V dc, 0.6-0.15 A
PoE Input: 48 V dc, 0.15 A
Digital Input: +13 to +30 V dc or +3 to -30 V dc, max 8 mA
Relay Output: 24 V dc, 1 A.
Mounting instructions:
Devices can be either DIN-rail or wall mounted.
Routine tests:
No Routine Tests are necessary.
[16] Descriptive Documents
The scheduled drawings are listed in the report no. provided under item no. [ 8 ] on page 1 of this Type Examination Certificate.
[17] Special Conditions of Use:
The equipment shall be installed in an enclosure that provides a degree of protection not less than IP 54 and accessible only by the
use of a tool in accordance with EN 60079-15.
Devices are for use in an area of not more than pollution degree 2 in accordance with EN 60664-1.
[18] Essential Health and Safety Requirements
Met by compliance with the standards EN 60079-0:2012+A11:2013, EN 60079-15:2010.
Additional information
The trademark will be used as the company identifier on the marking label.