Approval/Certificate/Document of Conformity

SCHEDULE
EU-TYPE EXAMINATION CERTIFICATE Sira 05ATEX1285X
Issue 5
This certificate and its schedules may only be
reproduced in its entirety and without change
CSA Group Netherlands B.V.
Utrechseweg 310,
6812 AR, Arnhem Netherlands
DQD 544.09 Rev 2018-04-20 Page 5 of 6
Issue
Date
Report number
Comment
1
26 June 2009
R51A20139C
This Issue covers the following changes:
All previously issued certification was rationalised
into a single certificate, Issue 1, Issue 0
referenced above is only intended to reflect the
history of the previous certification and has not
been issued as a document in this format.
The rationalisation of the certificate in accordance
with that listed in section 14.3.
2
22 March 2012
R27074A/00
The introduction of Sira Variation 4.
3
26 March 2013
R27876A/00
The rationalisation of the certificate in accordance with
that listed in section 14.3.
4
04 June 2018
R70144815B
This Variation introduced the following changes:
EC-Type Examination Certificate in accordance
with 94/9/EC updated to EU-Type Examination
Certificate in accordance with Directive
2014/34/EU.
(In accordance with Article 41 of Directive
2014/34/EU, EC-Type Examination Certificates referring to
94/9/EC that were in existence prior to the date of application
of 2014/34/EU (20 April 2016) may be referenced as if they
were issued in accordance with Directive 2014/34/EU.
Variations to such EC-Type Examination Certificates may
continue to bear the original certificate number issued prior to
20 April 2016.)]
The introduction of Sira Variation 6
5
15th October 2019
0462
Transfer of certificate Sira 05ATEX1285X
from Sira Certification Service to CSA Group
Netherlands B.V..
14.3 Certificate number BAS 01ATEX2271X Issue 10
15 SPECIFIC CONDITIONS OF USE (denoted by X after the certificate number)
15.1 Glands fitted with neoprene sealing rings (black) shall not be used in enclosures where the temperature,
at the point of mounting, is outside the range of -35C to +90C.
15.2 Glands fitted with silicone sealing rings (white or red) shall not be used in enclosures where the
temperature, at the point of mounting, is outside the range of 60°C to +180°C.
15.3 When the gland is used with reased safety and/or dust protected equipment, the entry thread shall be suitably
sealed to maintain the ingress protection rating of the associated enclosure.
15.4 If the KDSU, KISU and KOSU types of cable glands only grip the cable sheath of the cable and do not
clamp the cable armour or if they are used to terminate unarmoured, braided or screened cables, then
they shall only be used for fixed installations, hence, the cables shall be effectively clamped to prevent
pulling or twisting.
15.5 The KDSU and KISU cable glands, when installed in accordance with the manufacturer’s instructions
and with an appropriate enclosure on which they are fixed, are capable of providing an ingress protection
of IP66 and IP68 (50 metres 7 days).