Brief Description
The KDSW & KDSX type cable gland is for outdoor
use in the appropriate Hazardous Areas with
armoured cable. It gives environmental protection
to IP66 and IP68. A termination suitable for EMC
protection can be made using armoured cables with
these glands. KDSW type clamp steel wire armour
and KDSX types clamp woven steel wire and steel
tape armours.
Warning!
Please study carefully both pages of these
instructions before installation.
These glands should not be used in any application
other than those mentioned here or in our Data
Sheets, unless Weidmuller states in writing that the
product is suitable for such application. Weidmuller
can take no responsibility for any damage, injury or
other consequential loss caused where the glands are
not installed or used according to these instructions.
This leaflet is not intended to offer advice on the
selection of cable glands. Further guidance can be
found in the standards listed overleaf.
Interpretation of Markings
Markings on the outside of this gland carry the
following meanings: KDSW [a] [b] [c] [d] [e] [f] [ggg]
or alternatively KDSX [a] [b] [c] [d] [e] [f] [ggg]
Where: KDSW = Klippon
®
Double Seal for SWA
KDSX = Klippon
®
Double Seal for SWB/STA
[a] = Entry thread
[b] = Main component material
(B = brass, S = stainless steel)
[c] = Seal material
(S = silicone, N = Neoprene)
[d] = Continuity for lead sheath
(L = yes, O = no)
[e] = Plating
(Sc = self coloured, Ni = Nickel, Zi = zinc)
[f] = Reduced bore outer seal
(1 = yes, 2 = no)
[ggg] = Gland size (Gsss) (e.g. G20S)
Certificate Numbers
(ATEX) SIRA 05ATEX1286X
(IECEx) IECEx SIR 05.0067X
Protection Concept, EPLs and Gas Groups:
Ex d IIC Gb / Ex e IIC Gb / Ex ta IIIC Da
Environmental Protection:
IP66 / IP68 (50 metres for 7 Days)
ATEX (EU Directive 2014/34/EU) Markings:
T II 1D T II 2G
Special Conditions for Safe Use
1. These glands must not be used with enclosures
where the temperature at the point of mounting
exceeds -35°C to +90°C using neoprene seals,
or –60° to +180°C using silicone seals.
2. These glands, when installed in accordance
with the manufacturers instructions and with an
appropriate enclosure on which they are fixed, are
capable of providing an ingress protection of IP66
and IP68 (50 metres 7 days)
3. If these cable glands only grip the cable sheath of
the cable and do not clamp the cable armour or if
they are used to terminate unarmoured, braided
or screened cables, then they shall only be used
for fixed installations, hence the cables shall be
effectively clamped to prevent pulling or twisting.
4. Where glands without sealing rings are installed in
protection by enclosure (Ex t) equipment for use
in explosive dust atmospheres, they shall only be
fitted into enclosures offering a minimum of 5 full
threads, in accordance with EN 60079-31:2014
clause 5.1.2.