Brochure/Catalogue

D
Cable entries
D.312712630000
Klippon
®
cable glands – Nickel–plated Brass – Ex e, Ex d, IP66 / IP68 for armoured cables
/
'
/
'
6:
Cable gland for cables and lines with single-wire armouring and lead-sheath armouring.
Technical data
Material Brass, nickel-plated
Seal insert CR
Temperature range -35 °C...90 °C
Protection class IP54
Protection degree with GWDR IP66, IP68 - 2.5 bar
Water depth 25 m (30 Min.)
Type of armouring Single-wire armouring, Lead sheath armouring
Marking ATEX: II 2G, Ex db IIC Gb, Ex eb IIC Gb, II 1D, Ex ta IIIC Da, IECEx: Ex db IIC Gb, Ex eb IIC Gb, Ex ta IIIC Da
Certificate no. (ATEX / IECEx / EAC) SIRA 05ATEX1286X / IECEx SIR 05.0067X / RUC-DE.IT08.B.00594
Note
Length "L" depends on the cable diameter used. IP protection without GWDR is IP54. To achieve IP66 / IP68 protection, a nylon GWDR must be ordered separately.
Cable glands made of brass with natural surface are available in the online catalogue (catalog.weidmueller.com).
Ordering data
Type Thread D1 outer cable Ø D2 inner cable Ø Cable armour L/L1 SW SUHB Qty. Order No.
metric, nickel-plated brass
KDSW M20 BN L NI 1 G16 M 20 4.9-10.3 3.50-8.40 0.9 58 / 16 24 L24 20 1074660000
KDSW M20 BN L NI 2 G16 M 20 8.4-13.5 3.50-8.40 0.9 58 / 16 24 L24 20 1074690000
KDSW M20 BN L NI 1 G20 M 20 12-17.6 6.70-14.00 0.9-1.25 58 / 16 30 L30 20 1074760000
KDSW M20 BN L NI 2 G20 M 20 15.5-21.1 6.70-14.00 0.9-1.25 58 / 16 30 L30 20 1074780000
KDSW M20 BN L NI 1 G20S M 20 9.4-12.5 8.00-11.70 0.9-1.25 58 / 16 24 L24 20 1074720000
KDSW M20 BN L NI 2 G20S M 20 11.5-16 8.00-11.70 0.9-1.25 58 / 16 24 L24 20 1074740000
KDSW M25 BN L NI 1 G25 M 25 16.8-23.9 13.00-20.00 1.25-1.6 58 / 16 38 L38 20 1074810000
KDSW M25 BN L NI 2 G25 M 25 20.3-27.4 13.00-20.00 1.25-1.6 58 / 16 38 L38 20 1074830000
KDSW M32 BN L NI 1 G32 M 32 23.2-30.5 19.00-26.30 1.6-2 65 / 16 46 L46 10 1074850000
KDSW M32 BN L NI 2 G32 M 32 26.7-34 19.00-26.30 1.6-2 65 / 16 46 L46 10 1074860000
KDSW M40 BN L NI 1 G40 M 40 28.6-36.2 25.00-32.20 1.6-2 72 / 16 55 L55 10 1074870000
KDSW M40 BN L NI 2 G40 M 40 33-40.6 25.00-32.20 1.6-2 72 / 16 55 L55 10 1074880000
KDSW M50 BN L NI 1 G50 M 50 41.4-48.5 36.50-44.10 2-2.5 73 / 16 65 L65 1 1074920000
KDSW M50 BN L NI 2 G50 M 50 45.7-53.2 36.50-44.10 2-2.5 73 / 16 65 L65 1 1074930000
KDSW M50 BN L NI 1 G50S M 50 34.8-42.4 31.50-38.20 2-2.5 73 / 16 65 L65 1 1074890000
KDSW M50 BN L NI 2 G50S M 50 39.4-46.7 31.50-38.20 2-2.5 73 / 16 65 L65 1 1074910000
KDSW M63 BN L NI 1 G63 M 63 53.8-61.2 49.50-56.00 2.5 76 / 19 80 L80 1 1074960000
KDSW M63 BN L NI 2 G63 M 63 58.4-65.8 49.50-56.00 2.5 76 / 19 80 L80 1 1074970000
KDSW M63 BN L NI 1 G63S M 63 47.5-54.8 42.50-50.10 2.5 76 / 19 80 L80 1 1074940000
KDSW M63 BN L NI 2 G63S M 63 52.1-59.5 42.50-50.10 2.5 76 / 19 80 L80 1 1074950000
KDSW M75 BN L NI 1 G75 M 75 66.5-73.4 60.50-68.00 2.5 82 / 19 90 L90 1 1075010000
KDSW M75 BN L NI 2 G75 M 75 71.1-78 60.50-68.00 2.5 82 / 19 90 L90 1 1075020000
KDSW M75 BN L NI 1 G75S M 75 60.2-68 54.50-62.00 2.5 82 / 19 90 L90 1 1074980000
KDSW M75 BN L NI 2 G75S M 75 64.8-72.2 54.50-62.00 2.5 82 / 19 90 L90 1 1074990000
Note
All cable glands have a thread pitch of 1.5mm.
In the case of Ex d applications, the inner threads used for cable glands must meet the requirements of section 5.3 of EN/IEC 60079-1. In the screwed in position, at least 5 threads must be engaged.
If the cable glands are installed in non-metallic Ex e connection equipment, these must be connected to the protective earth of the system.
The connection cable must be laid securely and inflexibly to rule out tensile stress.
Installation specifications and tightening torques can be found in the installation instructions. For further information please use our online catalogue: catalog.weidmueller.com.
Ex-cable glands – Brass