Brochure/Catalogue
5
Technical data
Features
• For use in potentially explosive atmospheres and industrial applications
• Extremely robust with a high impact resistance
• Approved to the latest international standards
• M4 or M6 mounting elements integrated into enclosure body for installation of mounting plates, mounting rails, printed circuit boards etc.
Note: The enclosure range Klippon
®
POK can be assembled with terminals or other approved equipment by our locally available Application-Specic Solutions service. Please ask us for more details.
Ex Standard
Enclosure material Glass bre-reinforced polyester to DIN 16913 with added graphite Glass bre-reinforced polyester to DIN 16913
Surface Black, similar to RAL 9011 Grey, similar to RAL7001
IP Rating IP 66 IP 66
NEMA Rating *
Equipment mounting M4 to M6 threaded bushes M4 to M6 threaded bushes
Enclosure mounting 4 holes for M4 to M6 screw 4 holes for M4 to M6 screw
Lid xing M4/M6 slothead / crosshead screws from stainless steel M4/M6 slothead / crosshead screws from stainless steel
Impact Resistance 7J 7J
Gasket material Silicone (VMQ) Chloroprene
Temperature range -55 °C...+100 °C -40 °C...+100 °C
Torque screws of lid M4 2.0 – 2.5 Nm 2.0 – 2.5 Nm
Torque screws of lid M6 2.5 – 3.0 Nm 2.5 – 3.0 Nm
Surface resistance (in ohms) < 10
9
Ohm 10
12
Ohm
Flammability UL 94 V0, self extinguishing UL 94 V0, self extinguishing
Toxicity Halogen and cadmium-free Halogen and cadmium-free
Note
Approvals for empty enclosures
Ex Standard
Empty Enclosure Standard Ex EN 62208 Standard EN 62208
ATEX certicate IBExU 13ATEX1003 U
ATEX marking
T II 2G Ex e IIC Gb or T II2G Ex eb IIC
T II 2D Ex tb IIIC Db or T II 2D Ex tb IIIC
IECEx certicate IECEx IBE 13.0003U
IECEx marking Ex e IIC Gb or Ex eb IIC
Ex tb IIIC Db or Ex tb IIIC
GOST Ex *
GOST * *
cULus *
Lloyds Register *
Russian Maritime Register * *
Germanischer Lloyd *
Installation The Klippon
®
POK enclosure range can be pre-tted according to your wishes;
as an example, terminals, or other approved components, can be installed as required.Please ask for more details.
Note
This enclosure range is component certied. An additional certication is required, when other equipment will be installed into the enclosure.
*Approvals pending
Approvals terminal enclosures
Ex Standard
ATEX certicate IBExU13ATEX1004
ATEX marking
T II 2G Ex e IIC T6…T5 Gb or T II2G Ex eb IIC T6…T5
T II 1G Ex ia IIC T6…T5 Ga or T II 1G Ex ia IIC T6…T5
T II 2(1)G Ex e ia IIC T6…T5 Gb or T II 2(1)G Ex eb ia IIC T6…T5
T
II 2D Ex tb IIIC T 85 °C …100 °C Db or
T
II 2D Ex tb IIIC T 85 °C…100 °C
IECEx certicate IECEx IBE 13.0004X
IECEx marking Ex e IIC T6…T5 Gb or Ex eb IIC T6…T5
Ex ia IIC T6…T5 Gb or Ex ia IIC T6…T5
Ex e ia IIC T6…T5 Gb or Ex eb ia IIC T6…T5
Ex tb IIIC T 85 °C…100 °C Db or Ex tb IIIC T 85 °C…100 °C
Note If you have specic requirements for installations within potentially explosive atmospheres, please contact Weidmüller for a copy of the approval
certicates.
Overview