Brochure/Catalogue

Installation advice for instrumentation and control engineering
Surge protection for telephone signals U
ko
The VSPC U
ko
plug-in surge protector is used to protect up to
two phone lines with up to 4 wires.
The unprotected side points in the direction where the pulse
or interference is expected. The connecting cable’s shield
is connected to terminal 3 e. g. the Weidmüller clamping
bracket (KLBÜ) can be used.
The earthed DIN rail can then pick up the pulse and
discharge it to the earth.
PROTECTED
UNPROTECTED
8
10
12
2
4
6
1
3
5
7
9
11
VSPC TELE
Uk02WIRE
8924660000
U:180 V DC
C
I:0,45 A
N
C1 <1 kA 8/20
IP 20
U800 V
P
PE
La Lb
WE
b2
a2
NNF
APL APL
LbLaLbLa
La Lb
WE
b2
a2
NNF
For long cables, and especially for current loops, additional
protection is set-up at the sensors. The VSPC BASE FG
oating-earth base can be used there. A built-in gas
discharge tube makes this a “high impedance” earth, which
prevents an interference current on the shield.
B
B.1292028840000
Lightning and surge protection
for control and instrumentation signals