C.38 2028840000
Lightning and surge protection
for low voltage supply
Type II/III surge protection U
c
: 280V
Suitable for 230/400V mains systems
Leakage current free, pluggable arrester
Coded voltage level
High energy absorption with short time to sparkover
Insert can be rotated through 180°
No follow-on current
Installation in distribution board
Thermal protection function
Co-ordination with VPU Type I
Technical data
Rated voltage (AC)
Max. continuous voltage, Uc (AC)
Discharge current I
n
(8/20µs) wire-PE
Discharge current I
max
(8/20µs) wire-PE
Combined pulse U
OC
Requirements class, acc. to EN 61643-11
Short-circuit current rating I
SCCR
Leakage current at U
n
Fuse
Temporary surge voltage (over-voltage) - TOV
Protection level with I
N
(L/N-PE)
Response time
Optical function display
Design
Colour
Ambient temperature (operational)
Storage temperature
Connection according to IEC 947-7-1
Solid
Stranded
Stripping length
Tightening torque
Approvals
Approvals
Standards
Dimensions / Signalling contact info
Clamping range (nominal / min. / max.) mm²
Height x width x depth mm
Signalling contact
Note
Ordering data
without remote signalling contact
with remote signalling contact (R)
Note
Accessories
Note
VPU II 1 LCF / R 280 V / 40 KA
1-phase
8
2.
&+$1*(
230 V
280 V
20 kA
40 kA
10 kV
T2, T3
25 kA
30 µA
125 A gL (if back-up fuse > 125 A)
438 V
≤ 1.8 kV
≤ 100 ns
grey = ok, red = arrester is defective, replace it
Installation housing; 1TE, Insta IP 20
Black, Arrester red
-40 °C...70 °C
-40 °C...80 °C
1.5...16 mm²
1.5...50 mm²
15 mm
2...3 Nm
CE; EAC; OEVE
IEC61643-11, EN61643-11
no remote sig. contact with remote signalling (R)
16 / 1.5 16 / 1.5
94 / 17.8 / 69 105 / 17.8 / 69
No 250 V 1A 1CO
Type Qty. Order No.
VPU II 1 LCF 280V/40KA 1 1352740000
VPU II 1 R LCF 280V/40KA 1 1352750000
Pluggable spare arrester VPU II 0 LCF280 V/40 kA-1352730000
Type II surge protection