Brochure/Catalogue

D
D.18 2028840000
Lightning and surge protection
for data interfaces
Coax surge protection
Surge protection for COAX data networks
Metal housings
Surge protection using gas discharge tube
Easy handling using socket-adapter function, with
minimal attenuation
Technical data
Transmission capacity, max.
Max. continuous voltage, Uc (DC)
Characteristic impedance
Frequency range
Operating current, I
max.
Insertion loss
Return loss (attenuation)
Standing wave ratio, VSWR
Requirements category acc. to IEC 61643-21
Lightning test current I
imp
(10/350 µs)
Discharge current, max. (8/20 µs)
Response time
Protection level U
P
(typ.)
Earthing
Type of connection
Version
Ambient temperature (operational)
Approvals
Approvals
Standards
Dimensions
Clamping range (nominal / min. / max.)
Height x width
Note
Ordering data
Note
Accessories
Note
BNC Connector / M-F
Protection for video monitoring systems
25 W
90 V ± 20 %
50 Ω
0...3.5 GHz
10 A
< 0.2 dB
> 20 dB
< 1.2
D1, C3, C2, C1
5 kA
20 kA
≤ 100 ns
< 700 V
Required with M6 screw
Plug / socket
Adapter plug
-40 °C...80 °C
Plug / socket
/ 26
Type Qty. Order No.
BNC Connector / M-F 1 8947820000
N Connector / M-F
Protection for transmitters, GSM
25 W
90 V ± 20 %
50 Ω
0...3.5 GHz
10 A
< 0.15 dB
> 20 dB
< 1.2
D1, C3, C2, C1
5 kA
20 kA
≤ 100 ns
< 700 V
Required with M6 screw
Plug / socket
Adapter plug
-40 °C...80 °C
Plug / socket
/ 26
Type Qty. Order No.
N Connector / M-F 1 8947830000
Surge protection for data interfaces