Brochure/Catalogue

B
B.42 2028840000
Lightning and surge protection
for control and instrumentation signals
VSPC MOV - protection with varistor
unprotected
protected
Complete module, direct earthing
Complete module, direct earthing, with remote alert
Complete module, indirect earthing
Complete module, indirect earthing, with remote alert
unprotected
protected
unprotected
protected
unprotected
protected
1
5
2
6
3
4
91
0
7
11
8
12
GND
GND
TS
U
U
1
5
2
6
3
4
91
0
7
11
8
12
GND
GND
TS
U
U
X2
X1
FAULT
OK
1
5
2
6
3
4
91
0
7
11
8
12
GND
GND
TS
U
U
1
5
2
6
3
4
91
0
7
11
8
12
GND
GND
TS
U
U
X2
X1
FAULT
OK
Volume resistance 0.20 Ω
Overload - failure mode Mode 1
Requirements category acc. to IEC 61643-21 C1, C2, C3, D1
Surge current-carrying capacity C1 < 1 kA 8/20 μs
Surge current-carrying capacity C2 1.5 kA 8/20 μs
Surge current-carrying capacity C3 100 A 10/1000 μs
Surge current-carrying capacity D1 0.5 kA 10/350 μs
Discharge current I
n
(8/20 µs) wire-wire/wire-PE/GND-PE 0.2 kA / 2.5 kA / 0.5 kA
Discharge I
max
(8/20 μs) wire-wire/wire-PE/GND-PE 1.5 kA / / 1.5 kA
Lightning test I
imp
(10/350 µs) wire-wire/wire-PE/GND-PE 0.2 kA / / 0.5 kA
Type of connection Pluggable in VSPC BASE
Storage temperature -40 °C...80 °C
Ambient temperature (operational) -40 °C...70 °C
Protection degree IP20
Failure probability
λges 26
MTTF 4391
SIL in compliance with IEC 61508 3
Approvals
Approvals CE; CSAEX; EAC; GOSTEX; OEVE; TUEV; UL
Standards IEC 61643-21
Note
Dimensions of complete module (arrester + base element) no remote sig. contact
Height x width x depth mm 90 / 17.8 / 69
The associated VSPC base element should be ordered with this. The dimen-
sion information provided refers to the complete module.
Technical data
Pluggable arrester (impedance-neutral plugging/unplugging without
interruption)
Can be tested with the V-TEST testing device
Optional monitoring function with status display and alert functions
for MOV components
Version with floating-earth PE connection for avoiding voltage
potential differences
Tested in accordance with IEC 61643-21
Integrated PE foot, safely discharges up to 20kA (8/20 μs) and
2.5kA (10/350 μs) to PE
Base elements / base to arresters Ordering data for base
Description Type Qty. Order No.
Base element, direct earthing VSPC BASE 2/4CH 1 8924740000
Base element, direct earthing with remote contact VSPC BASE 2/4CH R 1 8951790000
Base element, indirect earthing with remote contact VSPC BASE 2/4CH FG R 1 8951800000
Base element, indirect earthing / floating earth FG VSPC BASE 2/4CH FG 1 8924300000
Note
Technical data can be found at the end of the VARITECTOR SPC section.
Order with VSPC CONTROL UNIT.
VARITECTOR SPC