Brochure/Catalogue

Quick and easy to operate
It only takes a few simple menu steps (in
German or English) to navigate directly to the
measurement function.
Ensures timely testing intervals
The portable V-TEST can be used to carry
out repeated testing in compliance with
IEC 62305-3.
Lightning
protection
level
Visual
inspection
Extensive
check
Extensive check
in critical
situations
a), b)
Year Year Year
I und II 1 2 1
III und IV 2 4 1
a) Lightning protection systems for
explosive structural facilities should be
visually inspected every six months. The
installation should be metrologically tested
once per year. To obtain ndings about
the seasonal uctuations, it is permissible
to take measurements at 14 to 15-month
intervals so as to determine the earth wire
circuit resistance at different times of the
year.
b) “Critical situations” could refer to
structural facilities containing systems
that are sensitive to interference or to
ofce buildings, commercial properties or
places where a large number of people
may reside.
V-TEST
B
B.612028840000
Lightning and surge protection
for control and instrumentation signals