Brochure/Catalogue

D
Cable entries
D.30 2712630000
Klippon
®
cable glands – Nickel–plated Brass – Ex e, Ex d, IP66 / IP68 for armoured cables
/
'
/
'
6:
Cable gland for cables and lines with single-wire armouring.
Technical data
Material Brass, nickel-plated
Seal insert Silicone
Temperature range -60 °C...180 °C
Protection class IP54
Protection degree with GWDR IP66, IP68 - 2.5 bar
Water depth 25 m (30 Min.)
Type of armouring Single-wire armouring
Marking ATEX: II 2G, Ex db IIC Gb, Ex eb IIC Gb, II 1D, Ex ta IIIC Da, IECEx: Ex db IIC Gb, Ex eb IIC Gb, Ex ta IIIC Da
Certificate no. (ATEX / IECEx / EAC) SIRA 05ATEX1286X / IECEx SIR 05.0067X / RUC-DE.IT08.B.00594
Note
Length "L" depends on the cable diameter used. IP protection without GWDR is IP54. To achieve IP66 / IP68 protection, a nylon GWDR must be ordered separately.
Cable glands made of brass with natural surface are available in the online catalogue (catalog.weidmueller.com).
Ordering data
Type Thread D1 outer cable Ø D2 inner cable Ø Cable armour L/L1 SW SUHB Qty. Order No.
metric, nickel-plated brass
KDSW M20 BS O NI 1 G16 M 20 4.9-10.3 3.50-8.40 0.9 58 / 16 24 L24 20 1136410000
KDSW M20 BS O NI 2 G16 M 20 8.4-13.5 3.50-8.40 0.9 58 / 16 24 L24 20 1136420000
KDSW M20 BS O NI 1 G20 M 20 12-17.6 9.30-14.00 0.9-1.25 58 / 16 30 L30 20 1136450000
KDSW M20 BS O NI 2 G20 M 20 15.5-21.1 9.30-14.00 0.9-1.25 58 / 16 30 L30 20 1136460000
KDSW M20 BS O NI 1 G20S M 20 9.4-12.5 8.00-11.70 0.9-1.25 58 / 16 30 L24 20 1136430000
KDSW M20 BS O NI 2 G20S M 20 11.5-16 8.00-11.70 0.9-1.25 58 / 16 24 L24 20 1136440000
KDSW M25 BS O NI 1 G25 M 25 16.8-23.9 13.00-20.00 1.25-1.6 58 / 16 38 L38 20 1136470000
KDSW M25 BS O NI 2 G25 M 25 20.3-27.4 13.00-20.00 1.25-1.6 58 / 16 38 L38 20 1136480000
KDSW M32 BS O NI 1 G32 M 32 23.2-30.5 19.00-26.30 1.6-2 65 / 16 46 L46 10 1136490000
KDSW M32 BS O NI 2 G32 M 32 26.7-34 19.00-26.30 1.6-2 65 / 16 46 L46 10 1136510000
KDSW M40 BS O NI 1 G40 M 40 28.6-36.2 25.00-32.20 1.6-2 72 / 16 55 L55 10 1136520000
KDSW M40 BS O NI 2 G40 M 40 33-40.6 25.00-32.20 1.6-2 72 / 16 55 L55 10 1136530000
KDSW M50 BS O NI 1 G50 M 50 41.1-48.5 36.50-44.10 2-2.5 73 / 16 65 L65 1 1136560000
KDSW M50 BS O NI 2 G50 M 50 45.7-53.2 36.50-44.10 2-2.5 73 / 16 65 L65 1 1136570000
KDSW M50 BS O NI 1 G50S M 50 34.8-42.4 31.50-38.20 2-2.5 73 / 16 65 L65 1 1136540000
KDSW M50 BS O NI 2 G50S M 50 39.4-46.7 31.50-38.20 2-2.5 73 / 16 65 L65 1 1136550000
KDSW M63 BS O NI 1 G63 M 63 53.8-61.2 49.50-56.00 2.5 76 / 19 80 L80 1 1136600000
KDSW M63 BS O NI 2 G63 M 63 58.4-65.8 49.50-56.00 2.5 76 / 19 80 L80 1 1136610000
KDSW M63 BS O NI 1 G63S M 63 47.5-54.8 42.50-50.10 2.5 76 / 19 80 L80 1 1136580000
KDSW M63 BS O NI 2 G63S M 63 52.1-59.5 42.50-50.10 2.5 76 / 19 80 L80 1 1136590000
KDSW M75 BS O NI 1 G75 M 75 66.5-73.4 60.50-68.00 2.5 82 / 19 90 L90 1 1136640000
KDSW M75 BS O NI 2 G75 M 75 71.1-78 60.50-68.00 2.5 82 / 19 90 L90 1 1136650000
KDSW M75 BS O NI 1 G75S M 75 60.2-68 54.50-62.00 2.5 82 / 19 90 L90 1 1136620000
KDSW M75 BS O NI 2 G75S M 75 64.8-72.2 54.50-62.00 2.5 82 / 19 90 L90 1 1136630000
Note
All cable glands have a thread pitch of 1.5mm.
In the case of Ex d applications, the inner threads used for cable glands must meet the requirements of section 5.3 of EN/IEC 60079-1. In the screwed in position, at least 5 threads must be engaged.
If the cable glands are installed in non-metallic Ex e connection equipment, these must be connected to the protective earth of the system.
The connection cable must be laid securely and inflexibly to rule out tensile stress.
Installation specifications and tightening torques can be found in the installation instructions. For further information please use our online catalogue: catalog.weidmueller.com.
Ex-cable glands – Brass