User Documentation

-59-
No.PF※※-OMP0002-H
Troubleshooting
If an operation failure of the product occurs, please confirm the cause of the failure from the following table.
If a cause applicable to the failure cannot be identified and normal operation can be recovered by
replacement with a new product, this indicates that the product itself was faulty.
Problems with the product may be due to the operating environment (installation etc). Please consult SMC.
Cross-reference for troubleshooting
Fault
Possible cause
Countermeasures
Display
No display.
Incorrect wiring.
Correct the wiring.
[Hi]/[Lo] is displayed
in turn.
Peak (Bottom) value display
function has been selected.
Refer to Peak/Bottom value display (page 54) and
turn off the function.
The display is
unstable.
Foreign matter in the
sensor.
Install a filter or mist separator on the IN side if there
is a risk of foreign matter entering the product.
If there is foreign matter on the mesh, remove it
completely, taking care not to damage the product.
The piping is connected in
the wrong direction.
Mount the product so that the flow direction is the
same as the arrow indicated on the side of the body
or the product label.
Pulsation in the flow.
It is possible that pulsation is generated due to the
fluctuation of the supply pressure or the
characteristics of the compressor or pump used as
the pressure source.
Change to a pressure source with less fluctuation or
install a tank which reduces the pressure fluctuation.
Air leakage.
Correct the piping.
Incorrect display.
Foreign matter in the
sensor.
Install a filter or mist separator on the IN side if there
is a risk of foreign matter entering the product.
If there is foreign matter on the mesh, remove it
completely, taking care not to damage the product.
The piping is connected in
the wrong direction.
Mount the product so that the flow direction is the
same as the arrow indicated on the side of the body
or the product label.
Incorrect units selected.
Select the correct unit using the unit selection
function.
Air leakage.
Correct the piping.
: Product with unit selection function.