User Documentation

Settings
30 1435710000/01/05.13
7.4 Settings
Make setting before measuring
Select setting item with <ITEM/> and press <SET>, the value will flash.
Set with <ITEM/> and <SHIFT/>.
Select [YES] in the confirmation window and press <SET> to confirm the setting values.
7.4.1 Settings for power measurement
Phase/wire system SYST
Select the phase/wire system to be measured.
Press <ITEM/>, <SHIFT/> to select the phase/wire system.
[Set list] 1P2W, 1P3W, 3P3W, 3P4W (initial: 1P2W)
* If the system settings do not match those of the measurement system, measurements will not be accurate.
CT type CT-T
Select using CT type (secondary side current).
Press <ITEM/>, <SHIFT/> to select CT type.
[Set list] 5 (5 A), 1 (1A) (initial: 5)
To use CT with secondary side current 5 A: [5]
To use CT with secondary side current 1 A: [1]