User Documentation

Communications
92 1435710000/01/05.13
Data register Name Unit Type of data Range: Hexadecimal
Function
code
01A2H Temperature 0.1°C Signed 16bit FC18H to 3E8H 03H
13B0H <LSB>
Export power conversion
value (1)
0.01 Unsigned 32bit 0H to 3B9AC9FFH 03H
13B1H <MSB>
13B2H <LSB>
Export power conversion
value (2)
0.01 Unsigned 32bit 0H to 3B9AC9FFH 03H
13B3H <MSB>
13B4H <LSB>
Export power conversion
value (3)
0.01 Unsigned 32bit 0H to 3B9AC9FFH 03H
13B5H <MSB>
13B6H <LSB>
Total export power
conversion value
0.01 Unsigned 32bit 0H to B2D05DFDH 03H
13B7H <MSB>
13E2H <LSB>
Conversion value (1) 0.01 Unsigned 32bit 0H to 3B9AC9FFH 03H
13E3H <MSB>
13E4H <LSB>
Conversion value (2) 0.01 Unsigned 32bit 0H to 3B9AC9FFH 03H
13E5H <MSB>
13E6H <LSB>
Conversion value (3) 0.01 Unsigned 32bit 0H to 3B9AC9FFH 03H
13E7H <MSB>
13E8H <LSB>
Total conversion value 0.01 Unsigned 32bit 0H to B2D05DFDH 03H
13E9H <MSB>
* ’Range’ is not the measurement range, but refers to the data range.
<LSB>: Least Significant Byte
<MSB>: Most Significant Byte
Notes
1) 03H: Read
06H/10H: Write
2) Data register unless specified is “0”.
3) If each setting value is written during communication, it is stored to internal memory at the same time.
Frequently changing the setting therefore reduces the life of the memory. Try to avoid doing this.
4) Data should be within the data range when written.