User Documentation

Communications
1435710000/01/05.13 95
Control code (C)
C
D7 D6 D5 D4 D3 D2 D1 D0
Transmission
direction
Slave response flag
Subsequent frame
flag
Function code
Item Contents
Transmission direction (D7) 0 Command frame from Master
1 Response frame from Slave
Slave response flag (D6) 0 Slave response is correct.
1 Slave response is wrong.
Subsequent frame flag (D5) 0 No subsequent data
1 With subsequent data
Function code (D4 to D0) 00000 Unassigned
01000 Not supported
10001 Read out data
10010 Not supported
10011 Read out transmission address (device number)
10100 Write data
10101 Write transmission address (device number)
10110 Not supported
10111 Change transmission speed
11000 Change password
11001 Not supported
11010 Reset integral power
11011 Not supported
Data field length (L)
Is the byte count of data field.
Read: L 200, Write: L 50, L = 0 means no data field.