User Documentation

Communications
98 1435710000/01/05.13
Read out transmission address
This reads out the transmission address (device number).
It is available only when the Master and Slave ratio is 1:1.
Command from master; Control code 13H
68H AAH AAH AAH AAH AAH AAH 68H 13H 00H CS 16H
Transmission address (AAH fix) Control code
Response from the Slave (normal)
68H A0 A1 A2 A3 A4 A5 68H 93H 06H
continue
Transmission address read out from Slave
continue
A0 A1 A2 A3 A4 A5 CS 16H
Transmission address read out from Slave
Note
1) No response if the Slave is abnormal.
Write data
It is only available by pressing the <MODE> key (programming key).
If the programming key is not pressed, there will be no response.
When writing data, an authorisation level (PA0) should be defined, but only ‘0’ is supported.
For an operator's'code, this will not be stored and the code is fixed to ‘0’.
Command from Master; Control code 14H
Data length (L): byte count of data identification + byte count of password authorisation level + byte count of
password + byte count of operator's code + byte count of data to write
68H A0 A1 A2 A3 A4 A5 68H 14H L
continue
Transmission address
(A0 to A5 or AAH)
Control code
continue
DI0 DI1 DI2 DI3 PA P0 P1 P2
continue
Data identification
Authorisation level
(33H fix)
Password
(P2:33H fix)
continue
C0 C1 C2 C3 N1 ••• Nm CS 16H
Operator's code (33H fixed) Writing data