User Documentation

Communications
102 1435710000/01/05.13
Reset integral power
This resets all integral power.
To reset integral power, an operator's code should be defined, but this will not be stored and the code is
fixed to ‘0’. It is only available only by pressing the <MODE> key (programming key).
Command from Master; control code 1AH
68H A0 A1 A2 A3 A4 A5 68H 1AH 08H
continue
Transmission address Control code
continue
PA P0 P1 P2
continue
Authorization
level (33H fix)
Password
(P2: 33H fix)
continue
C0 C1 C2 C3 CS 16H
Operator's code (33H fix)
Response from Slave (normal)
68H A0 A1 A2 A3 A4 A5 68H 9AH 00H CS 16H
Abnormal command from Slave
Control code (C); C0H (Response from slave is abnormal.) + Control code when error occurs.
68H A0 A1 A2 A3 A4 A5 68H C 01H ERR 16H
Control code
Error code
(bit flag)
Contents of
error code
Bit flag Contents
Bit 7 Not support
Bit 6 Not support
Bit 5 Not support
Bit 4 Not support
Bit 3
Impossible to change
transmission speed
Bit 2 Password mistake
Bit 1 No request data
Bit 0 Other errors