Derating curve
Economical and reliable supply even in extreme conditions:
single-phase PROtop versions with innovative DCL
technology for permanently reliable operation – even at
–40°C
The benets of DCL technology
Reliable triggering of circuit breakers
Dynamic and powerful motor starts
Additional power reserves
High-end power supplies need to perform efciently and reliably even in
challenging industrial environments. This requires high power reserves, a long
service life and optimal protection against surge voltage, vibration and extreme
temperatures.
PROtop power supplies have a particularly robust network input level and are
not sensitive to mechanical inuences. This guarantees reliable operation even in
challenging conditions such as those in wind power installations.
Thanks to the future-oriented DCL (dynamic current limiting) technology, high
pulse reserves are available at all times. The resulting dynamic range can be used
for the reliable triggering of circuit breakers or for powerful motor starts. At a
motor’s starting torque, for example, approx. 300% power reserve will be available
for approx. 100 ms, and 150% for approx. 5 s. For reliable tripping of line circuit
breakers, even 600% is available for 15 ms.
Outstanding peak load reserves thanks to DCL technology
PROtop meets the highest demands
VKRUWFLUFXLW
VZLWFK
SDUDOOHOORDG

,
3RZHU6XSSO\
²
The distance between the Power Supply and the load (l) is
measured under real conditions.
The following parameters are the basis of measurement:
Siemens circuit-breaker (5SY61xx-x)
The short circuit generated by a semiconductor switch
In addition to the short circuit current, the Power
Supply provides half of the nominal current for a parallel
connected load
(Status: April 2018)
Cable cross-section/mm² 0.75 1.0 1.5 2.5 4.0 6.0 10.0
PRO TOP1 72 W 24 V 3 A with DCL technology
Cable length with circuit breaker B2 /m 19 25 36.5 62 --- --- ---
PRO TOP1 120 W 24 V 5 A with DCL technology
Cable length with circuit breaker C2 /m 3.5 4.5 6.5 11 --- --- ---
PRO TOP1 240 W 24 V 10 A with DCL technology
Cable length with circuit breaker C2 /m 11 15 21.5 36.5 --- --- ---
Cable length with circuit breaker C4 /m 4 5 7.5 13 --- --- ---
Cable length with circuit breaker B6 /m 7 9.5 13.5 23 --- --- ---
PRO TOP1 120 W 12 V 10 A with DCL technology
Cable length with circuit breaker C2 /m 3 4 5.5 9.5 --- --- ---
Cable length with circuit breaker B6 /m 2.5 3.5 5 9 --- --- ---
PRO TOP1 480 W 24 V 20 A with DCL technology
Cable length with circuit breaker C2 /m 12 16.5 23.5 40 63 ≤ 95 ---
Cable length with circuit breaker C4 /m 8 10.5 15.5 25.5 42 64 ---
Cable length with circuit breaker C6 /m 3.5 4.5 7 12 18 29 ---
Cable length with circuit breaker B6 /m 11 14.5 21 35 55 ≤ 85 ---
Cable length with circuit breaker B10 /m --- 7.5 11 19 29.5 44 ---
Cable length with circuit breaker B16 /m --- --- 5 8.5 13 20 ---
PRO TOP1 960 W 24 V 40 A with DCL technology
Cable length with circuit breaker C2 /m 12.5 16.5 23 39 63 ≤ 95 ≤ 160
Cable length with circuit breaker C4 /m 8 11 15.5 26.5 42 64 ≤ 105
Cable length with circuit breaker C6 /m 4 5.5 8 13.5 21.5 33 57.5
Cable length with circuit breaker C10 /m --- 3 4.5 7.5 12 18 33
Cable length with circuit breaker C13 /m --- --- 2.5 4 6.5 9.5 17
Cable length with circuit breaker B6 /m 11 14.5 21 35 57 ≤ 80 ≤ 140
Cable length with circuit breaker B10 /m --- 7.5 11 19 30 46 ≤ 75
Cable length with circuit breaker B16 /m --- --- 5.5 9.5 15 24 42
Cable length with circuit breaker B20 /m --- --- --- 6 9.5 15 24
Cable length with circuit breaker B25 /m --- --- --- 4.5 7.5 11 20
PRO TOP1 480 W 48 V 10 A with DCL technology
Cable length with circuit breaker C2 /m 30 40 58 ≤ 95 ≤ 155 ≤ 235 ---
Cable length with circuit breaker C4 /m 13 20 27 49 61 105 ---
Cable length with circuit breaker B6 /m 20 30 40 67 ≤ 110 ≤ 170 ---
PRO TOP1 960 W 48 V 20 A with DCL technology
Cable length with circuit breaker C2 /m 29 39 58 ≤ 95 ≤ 310 ≤ 470 ≤ 400
Cable length with circuit breaker C4 /m 15.5 21 29 50 81 ≤ 240 ≤ 210
Cable length with circuit breaker C6 /m 5.5 8 11 20 31 48 ≤ 80
Cable length with circuit breaker B2 /m 68 91 ≤ 130 ≤ 220 ≤ 350 ≤ 530 ≤ 915
Cable length with circuit breaker B4 /m 35 45 68 ≤ 110 ≤ 180 ≤ 275 ≤ 470
Cable length with circuit breaker B6 /m 21 29 40 68 ≤ 110 ≤ 165 ≤ 290
Cable length with circuit breaker B10 /m 8.5 12.5 17 29 46 70 < 120
DCL – project planning table showing the maximum cable lengths for selective fuse triggering