Brochure/Catalogue

B
B.28 2737920000
Complete modules
Space-saving, 6.4 mm wide
3 time functions
Complete module with 1 CO relay (AgSnO)
PUSH IN and screw connection
6.4 mm
87.8 mm
89.4 mm
80.8 mm
ON DIP
12345678
6.4 mm
87.8 mm
89.6 mm
80.8 mm
ON
DIP
1
23456
7
8
PUSH IN connection Screw connection
Technical data
Control side
Rated control voltage
Power rating
Status indicator
Repeat accuracy
Basic accuracy
Setting tolerance
Min. pulse duration
Time ranges
Max. reset time after voltage interruption
Load side
Rated switching voltage
Max. switching voltage, AC
Max. switching voltage, DC
Continuous current
AC switching capacity (resistive), max.
DC switching capacity (resistive), max.
Max. switching frequency at rated load
Contact type
Mechanical service life
General data
Ambient temperature (operational)
Storage temperature
Humidity
Version
Resistance to vibration EN 61812-1
Approvals
Insulation coordinates
Rated voltage
Creepage and clearance distance input – output
Dielectric strength, Input/Output
Impulse withstand voltage
Protection degree
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth x width x height mm
Note
Ordering data
PUSH IN connection
Screw connection
Note
Accessories
Note
TR T 24 V DC 1CO M3
DC-Input
A2
A1
A1
A2
14 11 12
18
NO
COM
15
16
NC
TIMER
CURCUIT
Duo-LED
24 V DC ± 20 %
280 mW
Duo-LED orange: relay output on, Green duo-LED lit: supply voltage on,
Green duo-LED flashes: incorrect configuration, no function
± 1 %
≤ 5% (of scale-end value)
5 %
50 ms
0.01 s - 0.1 s, 0.1 s - 1 s, 1 s - 10 s, 10 s - 100 s
50
250 V AC
250
250 V
6 A
1500 VA
144 W @ 24 V
0.1 Hz
1 CO contact (AgSnO)
5 x 10
6
switching cycles
-20 °C...60 °C
-40 °C...85 °C
5-95% relative humidity, T
u
= 40°C, without condensation
CE; cULus; EAC
250 V
≥ 6 mm
4 kV
eff
/ 1 Min.
6 kV (1.2/50 µs)
IP20
PUSH IN connection Screw connection
1.5 / 0.14 / 2.5 1.5 / 0.14 / 2.5
88 / 6.4 / 90 88 / 6.4 / 90
Type Qty. Order No.
TRP T 24VDC 1CO M3 10 2639730000
TRS T 24VDC 1CO M3 10 2639560000
Further approvals and technical data can be found at catalog.weidmueller.com
Accessories: refer to the TERMSERIES Accessories page.
A1 / A2
15 / 18
T
On Delay
A1 / A2
Blinker
15 / 18
LED Gn*
TTTT
A1 / A2
15 / 18
T
One Shot
LED Or*
LED Or*
LED Gn*
LED Or*
LED Gn*
*LED Or = LED Orange
LED Gn = LED Green
0,5s
t
<
T
Resistive load
400
300
200
100
10
0.11
5
DC load breaking capacity
Voltage [V]
Current [A]
Switching Operations
0123456
Switching current (A)
10
4
10
5
10
6
230 V AC resistive load
Electrical endurance
Universal range
TERMSERIES TIMER