5.3 Specifications
Input types
Thermocouple Range -200...+1820 °C
Types B, E, J, K , L, N, R, S, T to IEC 60584 plus custom specific
RTD 2, 3, 4 wire, within the range -200...+850 °C, for Pt100, Pt1000 to
IEC 60571 and for Ni100 / Ni1000 to DIN 43760, for Cu10 and,100 plus
custom specific
Potentiometer 10 ...100 k
Resistance 10 ...5 k
Frequency 2 Hz...100 kHz
Voltage within the range -200...600 mV (min span 4 mV),
within the range -20...50 V DC (min span 0.5 V)
Current within the range -20...50 mA (min span 1 mA)
Current Loop supply +24 V DC
Sensor break output Selectable between -2% and 102% output
Analogue Output
DC voltage
0...5, 1...5, 0...10, 2...10 V or span-settable between -10...10 V
(min span 2.5 V)
DC current
0...20, 4...20, 0...10 mA, or span-settable between 0...20 mA
(min span 5 mA)
Max load (current / voltage)
700 / >10 k (>20 k for -10 V…+10 V)
Action
Direct or Reverse Acting
Digital Output Relay
Relays 2 x SPCO
Max voltage and current AC 250 V AC / 2 A
Max voltage and current DC 30 V DC / 2 A
General Data
Rated voltage 24...240 V AC/DC
24…36 V AC / 24…50 V AC (ATEX Zone 2)
Min. / max. power supply (ac-
cording VDE)
18…264 V AC/DC
18…40 V AC / 18…56 V DC (ATEX Zone 2)
Rated power < 3,5 W
Ambient operating range -40...+70 °C
Isolation test 1,5 kVeff / 1 min. between PE and power supply, as well as between PE
and input or output
2,5 kVeff / 1 min between input and output