Brochure/Catalogue

B
B.114 2737920000
DRI KIT with PUSH IN connection
2 CO contact, AC/DC coil
&LUFXLWGLDJUDP
$&FRLO/('
'&FRLO/('GLRGH
$
$





$
$





Load side
Rated switching voltage / Continuous current 250 V AC / 5 A
Max. switching voltage, AC 250 V
Min. switching power 10 mA @ 24 V, 10 mA @ 12 V, 100 mA @ 5 V
Contact type 2 CO contact with test button (AgSnO)
Mechanical service life 10 x 10
6
switching cycles
Max. switching frequency at rated load 0.1 Hz
General data
Ambient temperature (operational) -40 °C...55 °C
Storage temperature -40 °C...85 °C
Humidity 35...85 % rel. humidity, no condensation
Approvals CE; EAC
Insulation coordinates
Rated voltage 250 V
Impulse withstand voltage 5 kV (1.2/50 µs)
Dielectric strength, Input/Output 5 kV
eff
/ 1min
Dielectric strength of neighbouring contacts 1.5 kV
eff
/1 min.
Dielectric strength to mounting rail
Creepage and clearance distance input – output ≥ 3 mm
Overvoltage category III
Pollution degree 2
Dimensions PUSH IN
Clamping range (nominal / min. / max.) mm² 1.5 / 0.14 / 1.5
Depth x width x height see dimensioned drawing
Note
Further technical data can be found at catalog.weidmueller.com
Electrical endurance
Switching operations
Switching current [A]
10
4
10
5
10
7
10
6
250 V AC inductive load
(cos
φ = 0,4
)
30 V DC inductive load
(L/R = 7 ms)
123
456
0
250 V AC / 30 V DC
resistive load
DC load braking capacity
Resistive Load
Switching voltage [V DC]
Switching current [A]
0.1 51
1020.5
300
200
100
50
40
30
20
0.2
10
Operating voltage range [DC]
2,2
2,0
1,6
1,2
1,0
0,6
0,2
0 +20 +40 +60 +80 +100
Coil voltage [U/Un]
Ambient temperature [°C]
0,4
0,8
1,4
1,8
Operating voltage range [AC]
2,2
2,0
1,6
1,2
1,0
0,6
0,2
0 +20 +40 +60 +80 +100
Coil voltage [U/Un]
Ambient temperature [°C]
0,4
0,8
1,4
1,8
Dimensioned drawing without test button
62.7 mm
58.9 mm
102.1 mm
Dimensioned drawing with test button
62.7 mm
58.9 mm
102.1 mm
Applications
Technical data
Mounted kit consisting relay, socket and retaining clip
100 % function tested
100 % check of the dielectric strenght between input - output
Optional: test button with coloured control voltage marking (AC coil:
red / DC coil: blue)
Bright status LED (AC coil: red / DC coil: green)
Universal range
D-SERIES – relay modules