Brochure/Catalogue

C
C.110 2737920000
SIL3 relay
Unresponsive to test pulses from the Triconex
®
output
modules
Proof of compatibility is available for use with the
Tricon
TM
,Trident
TM
and Tri-GP
TM
systems.
Externally accessible fuse
TÜV-certified “Approved Safety Function”
Technical data
Temperatures
Ambient temperature (operational)
Storage temperature
Input (safety circuit) (A1, A2)
Rated control voltage
Power consumption
Status indicator
Output (safety circuit) (13, 14, 15)
Contact design
max. switching current, internal fuse
max. switching current, external fuse
max. permitted switching voltage
max. permitted switching current
min. switching power
max. switching power
Switch-on time
Base material of the contact
Internal fuse
External back-up fuse
Short-circuit-proof
Insulation coordinates
Rated voltage
Creepage and clearance distance input – output
Dielectric strength, Input/Output
Dielectric strength to mounting rail
Impulse withstand voltage
Overvoltage category
Pollution degree
Further details of approvals / standards
Standards
Approvals
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth x width x height mm
Note
Ordering data
with monitoring
Note
SCS 24 V DC P1SIL3DS I
1.5 / 0.13 / 2.5
114.1 / 22.5 / 117.3
-25...50 °C
-40...85 ° C
24 V DC (16...36 V DC)
50 mA
LED yellow
1 x de-energised to safe (NO contact)
5 A
5 A
250 V AC / 30 V DC
5 A
10 mA @ 12 V
1250 VA
≤ 25 ms
AgNi
5 A time-lag
5 A time lag
No
300 V
≥ 6 mm
3.51 kV
eff
/5 s
6 kV (1.2/50 µs)
III
2
EN 61010-2-201:2013 + AC:2013, EN 61326-1:2013, EN 61326-3-
1:2008, EN 61326-3-2:2008
CE; cULus; EAC; FUSAFETY
Type Qty. Order No.
SCS 24VDC P1SIL3DS I 1 2500980000
The SCS 24VDC P1SIL3DS I safety
relay is used in areas
that
require a functionally safe shutdown. This component
fulfils the
requirements of EN 61508, SIL 3.
A1
A2
15
T2
T1
14
13
Logic
117.3 mm
114.1 mm
107.1 mm
22.5 mm
Application range
Functional safety – SAFESERIES SIL relays