Brochure/Catalogue
C
C.1112737920000
SIL3 relays
• Energized/de-energized to safe
• All-pole disconnection possible
• Test inputs for testing the relay contacts
• Externally accessible fuse
• TÜV-certified “Approved Safety Function”
Technical data
Temperatures
Ambient temperature (operational)
Storage temperature
Input (safety circuit) (A1, A2)
Rated control voltage
Guaranteed current consumption of 24 VDC -10%
Power consumption
Status indicator
Test inputs (X1, X2, X3)
Rated control voltage
Status indicator
Number of test inputs
Output (safety circuit) (13, 14, 23, 24)
Contact design
max. switching current, internal fuse
max. switching current, external fuse
max. permitted switching voltage
max. permitted switching current
min. switching power
max. switching power
Switch-on time
Base material of the contact
Internal fuse
External back-up fuse
Short-circuit-proof
Insulation coordinates
Rated voltage
Creepage and clearance distance input – output
Creepage and clearance distance output – output
Dielectric strength, Input/Output
Dielectric strength output – output
Dielectric strength to mounting rail
Impulse withstand voltage
Overvoltage category
Pollution degree
Further details of approvals / standards
Standards
Approvals
Dimensions
Clamping range (nominal / min. / max.) mm²
Depth x width x height mm
Note
Ordering data
Note
SCS 24 V DC P2SIL3DSES
1.5 / 0.13 / 2.5
114.1 / 22.5 / 117.3
-25 °C...50 °C
-40 °C...85 °C
24 V DC -15 / +20%
35 mA
45 mA
LED yellow
24 V DC
LED red flashing: test input is triggered
2
1 x de-energised to safe (NO contact), 1 x energised to safe (NO
contact)
5 A (refer to derating curve)
5 A (refer to derating curve)
250 V AC
5 A
10 mA @ 12 V
1250 VA
< 5.5 ms (DTS), < 5 ms (ETS)
AgNi 0.15 gold flashed
5 A time-lag
5 A time lag
No
300 V
≥ 5.5 mm
≥ 5.5 mm
4 kV
eff
/ 1 min
4 kV
eff
/ 1 min
4 kV
eff
/ 1 Min.
6 kV (1.2/50 µs)
III
2
EN 50178, EN 61000, EN 61326-3-2
CE; EAC; FUSAFETY
Type Qty. Order No.
SCS 24VDC P2SIL3DSES 1 1319270000
7KHVDIHW\U
HOD\6&69'&36,/'6(6LVXVHGLQDUHDV
WKDW
UHTXLUHIXQFWLRQDOO\VDIHGHDFWLYDWLRQRUDFWLYDWLRQ
7KH
UHTXLUHPHQWVDFFRUGLQJWR(16,/FDQEH
IXOILOOHGZLWKWKLVPRGXOH
5(/$<
287387
$7
9
'&
9
/RJLF,QSXW
9
'&
9
7HVW,QSXW
PD[9$&
VZLWFKLQJYROWDJH
6DIHW\287
)
7(67
$ $ ; ; ;
Application range
Functional safety – SAFESERIES SIL relays