Product Change Notification
Copyright © 2020 Weidmüller Interface GmbH & Co. KG 2 / 2
All rights reserved. Reproduction without permission is prohibited.
• The feature of the PROCON-WEB Designer to search for valid u-control targets in the network does not work
stable when multiple network adapters are used.
Workaround: Disabling all other network adapters of the engineering PC, but the one connected to the
u-control studio enables the search mechanism of the Designer properly.
• When numeric data types are changed in the PLC project the variables may not recognized properly by the
PROCON-Web runtime until the u-control is restarted.
• The status page of the u-create PROCON-WEB runtime “deviceIP:16701” shows wrong hardware
specifications (Storage is labelled as HDD with no value)
• Endless loops are programmable via the scripting feature without error messages to warn the user.
• Creating endless loops make the runtime unresponsive and disable the streaming of new projects to the
runtime.
• Scripting with local variables does not work properly.
• Missing options to configure alarm boxes properly.
• Landscape screen orientation is not working when using smart phones as clients.