Firmware change log of the device: 1334950000 UC20-WL2000-AC
Firmware updating information:
An update of the firmware can be done via the graphical web front end. A description of the firmware update
procedure can be found in the device manual on the Weidmüller website: www.weidmueller.com
Version 1.11.0 Hardware Version 01.xx.xx Release date: January, 2020
New features:
• User management: access restriction for user ‘service’ regarding real-time application and factory reset.
Information:
• ATTENTION: Upgrading firmware prior to 1.10 requires two steps. 1. Flash firmware image UC20-WL2000-
RS-1.10.0.swu and restart system. 2. Flash target firmware version 1.11. Otherwise update fails with error
message: "File is too big".
• Firefox: 'Private Mode' is not supported.
Known issues:
• Application: 'REAL_TO_TIME' values are not displayed in full precision which may lead to problems in
comparison operations.
• Remove a module after Autoscan operation and the follow up deploy operation fails. A power cycle is
necessary to solve this error.
Version 1.10.0 Hardware Version 01.xx.xx Release date: November, 2020
New features:
• User management: additional user 'service'
• File copy service based on scp.
• FBD Editor: dialogue for editing variables and introduced 'typed values' in diagrams.
• Web access is switched to HTTPS protocol.
• Node-RED: upgrade to version 1.1.2
Information:
• ATTENTION: Upgrade to firmware 1.10 requires two steps. 1. Flash firmware image UC20-WL2000-RS-
1.10.0.swu and restart system. 2. Flash target firmware version 1.10. Otherwise update fails with error
message: "File is too big".
• Note: After firmware update the "admin" password is reset to the default value.
• The new introduced HTTPS protocol requires a user confirmation for an unsecure browser connection. Please
confirm the connection type with the first web access.
• Firefox: 'Private Mode' is not supported.
Bug fixes:
• Node-RED: 'iodata-out' supports to set values with variable of type 'TIME'.
• FBD Editor: conversion block behaves according to IEC 61131.
• PID controller: freezes when using out of bound value.
• Visu: Title not shown while editing for diagram or chart widgets.
• swupdate mode for Ethernet port X2 is possible
Known issues:
• Application: 'REAL_TO_TIME' values are not displayed in full precision which may lead to problems in
comparison operations.
• Remove a module after Autoscan operation and the follow up deploy operation fails. A power cycle is
necessary to solve this error.
Version 1.9.0 Hardware Version 01.xx.xx Release date: August, 2020
New features:
• Modbus RTU: support of multi register access and triggers.
• Smart Visu: support of multiple pages.
• FBD Editor: support of unconnected inputs.
• FBD Editor: improved display of comments in FBD diagrams.
• Node-RED: support nodes with native dependencies.
• Node-RED: added S7 protocoll (RFC1006) and Telegram Nodes.
• OPC-UA: improvement of Web-UI.
• OPC-UA: added operating state indicator.