Product Change Notification

Copyright © 2014-2017 Weidmüller Interface GmbH & Co. KG 2 / 5
All rights reserved. Reproduction without permission is prohibited.
UR20-4AI-R-HS-16-DIAG (2001670000)
Version 01.00.01 Release date: June 06, 2016
First released version
UR20-4AI-RTD-DIAG (1315700000)
UR20-4AI-TC-DIAG (1315710000)
Version 01.00.11 Release date: December 2017
Fixed that deactivation of Limited Value Monitoring sometimes causes faulty behaviour.
Version 01.00.10 Release date: May 17, 2017
Bug fix: Linearization curve for CU10 sensors >200°C corrected
UR20-4AI-RTD-HP-DIAG (2456540000)
Version 01.00.02 Release date: December 2017
Fixed that deactivation of Limited Value Monitoring sometimes causes faulty behaviour.
Version 01.00.01 Release date: May 17, 2017
First released version
High precision RTD module
Supports additional LG-Ni1000 sensor characteristic
Supports additional PT100 from -200°C to +250°C
UR20-4AI-UI-12 (1394390000)
UR20-4AI-UI-16[-HD] (1315620000, 1506920000),
UR20-4AI-UI-16-DIAG[-HD] (1315690000, 1506910000),
UR20-8AI-I-16-[DIAG]-HD (1315650000, 1315720000)
UR20-8AI-I-PLC-INT (1315670000)
Version 01.02.01 Release date: June, 2020
Bug fix for 8 channel HD modules: Correct behaviour of diagnosis and status LED for undervoltage detection
Bug fix for 4 channel modules: Improved shortcut behaviour
Version 01.02.00 Release date: August, 2019
Bug fix: Fixed that module sometimes remains in fault state when (re-)booted at high temperature.
Version 01.01.00 Release date: July, 2019
Changed the value range for the FORCE mode of the webserver, now low-level values for the range of
underloading can be set
Fixed that the channel error LED stays off when lower or upper limits are exceeded
Reduced the crosstalk between the input channels
Removed toggling diagnosis between “Overload” and “Upper limit value exceeded”, when an input channel
is overloaded
Adjusted behaviour of module diagnostics:
- Module diagnostics are always active (in case of an error the module status LED will be red)
- In case of an error the channel error LED will always be red on modules which are supporting
single channel diagnostic, independent of the configuration for the diagnostic
Version 01.00.36 Release date: May 17, 2017
New feature: Additional low pass implemented
Version 01.00.34 Release date: October 04, 2016
New feature: Adaptation of the switching thresholds
according to Namur Recommendation NE43
Standardization of the Signal Level for the Failure
Information of Digital Transmitters”
High limits: +5%
Low limits: -10% for non zero unipolar range
Limits for bipolar range: +/-10%
Version 01.00.33 Release date: June 06, 2016
First released version
UR20-4AI-UI-DIF-16-DIAG (1993880000)
Version 01.04.00 Release date: September 2019
Bug fix: Fixed that module sometimes remains in fault state when (re-)booted at high temperature.
Version 01.03.05 Release date: December 2017
Measurement range
Low limits
High limits
0 to 20mA
n.a.
> 21mA
4 to 20mA
< 3.6mA
> 21mA
0 to 10V
n.a.
> 10.5V
2 to 10V
< 1.8V
> 10.5V
+/-10V
< -10.5V
> 10.5V
0 to 5V
n.a.
> 5.25V
1 to 5V
< 0.9V
> 5.25V
+/-5V
< -5.25V
> 5.25V