Product Change Notification
Copyright © 2014-2017 Weidmüller Interface GmbH & Co. KG 2 / 5
All rights reserved. Reproduction without permission is prohibited.
UR20-4AI-R-HS-16-DIAG (2001670000)
Version 01.00.01 Release date: June 06, 2016
• First released version
UR20-4AI-RTD-DIAG (1315700000)
UR20-4AI-TC-DIAG (1315710000)
Version 01.00.11 Release date: December 2017
• Fixed that deactivation of Limited Value Monitoring sometimes causes faulty behaviour.
Version 01.00.10 Release date: May 17, 2017
• Bug fix: Linearization curve for CU10 sensors >200°C corrected
UR20-4AI-RTD-HP-DIAG (2456540000)
Version 01.00.02 Release date: December 2017
• Fixed that deactivation of Limited Value Monitoring sometimes causes faulty behaviour.
Version 01.00.01 Release date: May 17, 2017
• First released version
• High precision RTD module
• Supports additional LG-Ni1000 sensor characteristic
• Supports additional PT100 from -200°C to +250°C
UR20-4AI-UI-12 (1394390000)
UR20-4AI-UI-16[-HD] (1315620000, 1506920000),
UR20-4AI-UI-16-DIAG[-HD] (1315690000, 1506910000),
UR20-8AI-I-16-[DIAG]-HD (1315650000, 1315720000)
UR20-8AI-I-PLC-INT (1315670000)
Version 01.02.01 Release date: June, 2020
• Bug fix for 8 channel HD modules: Correct behaviour of diagnosis and status LED for undervoltage detection
• Bug fix for 4 channel modules: Improved shortcut behaviour
Version 01.02.00 Release date: August, 2019
• Bug fix: Fixed that module sometimes remains in fault state when (re-)booted at high temperature.
Version 01.01.00 Release date: July, 2019
• Changed the value range for the FORCE mode of the webserver, now low-level values for the range of
underloading can be set
• Fixed that the channel error LED stays off when lower or upper limits are exceeded
• Reduced the crosstalk between the input channels
• Removed toggling diagnosis between “Overload” and “Upper limit value exceeded”, when an input channel
is overloaded
• Adjusted behaviour of module diagnostics:
- Module diagnostics are always active (in case of an error the module status LED will be red)
- In case of an error the channel error LED will always be red on modules which are supporting
single channel diagnostic, independent of the configuration for the diagnostic
Version 01.00.36 Release date: May 17, 2017
• New feature: Additional low pass implemented
Version 01.00.34 Release date: October 04, 2016
• New feature: Adaptation of the switching thresholds
according to Namur Recommendation NE43
“Standardization of the Signal Level for the Failure
Information of Digital Transmitters”
High limits: +5%
Low limits: -10% for non zero unipolar range
Limits for bipolar range: +/-10%
Version 01.00.33 Release date: June 06, 2016
• First released version
UR20-4AI-UI-DIF-16-DIAG (1993880000)
Version 01.04.00 Release date: September 2019
• Bug fix: Fixed that module sometimes remains in fault state when (re-)booted at high temperature.
Version 01.03.05 Release date: December 2017
Measurement range
Low limits
High limits
0 to 20mA
n.a.
> 21mA
4 to 20mA
< 3.6mA
> 21mA
0 to 10V
n.a.
> 10.5V
2 to 10V
< 1.8V
> 10.5V
+/-10V
< -10.5V
> 10.5V
0 to 5V
n.a.
> 5.25V
1 to 5V
< 0.9V
> 5.25V
+/-5V
< -5.25V