User Documentation
3 System description of safe I/O modules | Processing time
14 1484600000/07/11.2020u-remote IP20 modules for functional safety manual
1
2
3
4
1
2
3
4
1
2
3
4
+24 V DC
GND
DI X
AUX-O X
AUX-O Y
DI Y
+24 V DC
DI X (PN)
AUX-O X
AUX-O Y
DI Y (P)
+24 V DC
DI X (PN)
AUX-O X
AUX-O Y
DI Y (P)
GND module
Example for the operation without own test pulses
In the event that the module shall be used as
typeA source with disabled test pulses the DIX
input must be parameterised N-switching.
1
2
3
4
DI X (N)
AUX-O X
AUX-O Y
DI Y (P)
Operation without own test pulses, typeA source with N-switching DIX
3.8 Processing time
The processing time of a signal within the safety chain can
be calculated as follows:
Input delay (parameterised)
+ Response time input
+ Response time output
+ Data transfer from and to the PLC
+ PLC computing time
= Processing time
The response times of the inputs and the outputs of safe
I/O modules are indicated in the technical data tables.