User Documentation

6 Installation and replacement
71u-remote IP20 modules for functional safety manual 1484600000/07/11.2020
WARNING
Explosion risk!
Before assembly or replacement, make
sure that there is not a potentially explo-
sive atmosphere!
For applications in potentially explosive
atmospheres, observe the installation and
construction requirements of EN60079-
15 and/or country-specific regulations.
WARNING
Dangerous contact voltage!
All work on the u-remote station must be
carried out with the power supply discon-
nected.
Make sure that the place of installation
(switch cabinet etc.) has been
disconnected from the power supply!
ATTENTION
The product can be destroyed by elec-
trostatic discharge!
The components in the u-remote series can
be destroyed by electrostatic discharge.
Please make sure that personnel and work
equipment are sufficiently earthed!
Carry out all work during the installation and removal as
well as replacement of components as described in the
u-remote manual.
When using modules for functional safety (safe I/O modules
or safe power-feed modules), please observe the following
additional notes:
The modules may only be installed in lockable switch
cabinets which meet protection class IP54.
Please use wire-end ferrules in combination with flexible/
multi-conductor cables.
Ensure that external short circuits due to the cabling can-
not occur for safety inputs in the configuration without
test pulses (see DINENISO13849-2 Table D.4).
Once an electronic unit is removed from a safe
power-feed module, the inputs and outputs of the
subsequent modules are no longer supplied with
power. This is equivalent to triggering the con-
nected safety equipment!
6 Installation and replacement