User Documentation

7 Example applications | Dual-channel safety door monitoring, magnetically operated interlock with manual reset and emergency stop
84 1484600000/07/11.2020u-remote IP20 modules for functional safety manual
Achievable safety rating Category 4 ENISO13849-1
PLe ENISO13849-1
SIL 3 EN62061/61508
Stop category 0 EN60204-1
Features Dual-channel monitoring
Cross-connection detection
Manual reset
Monitoring of external contactors
(EDM)
Off-delay via PLC
Safety sensor/operating
mechanism
Emergency stop button
Position switch with interlock
Notes Exclusion of the fault “Interruption or
releasing of the activator, error in the
safety interlock”
The PLC must activate the interlock
directly after the safety door is closed
All examples shown are proposals without war-
ranty. In any case the operator has to perform a
safety review of the entire site.
M
1.1
1.2
1.3
1.4
3.1
3.2
3.3
3.4
4.1
4.2
4.3
4.4
1.1
1.2
1.3
1.4
1.1
1.2
1.3
1.4
1.1
1.2
1.3
1.4
2.1
2.2
2.3
2.4
2.1
2.2
2.3
2.4
3.1
3.2
3.3
3.4
4.1
4.2
4.3
4.4
K4
K3
K4
K3
K4K3Reset
S2S4
S3
UR20-PF-O-xDI-SIL UR20-4DO-P
UR20-4DI-PUR20-4DO-P
L+(+24 V)
M (0 V)
S1
Safety door
(closed)
Emergency stop
Example application for dual-channel safety door monitoring, magnetically operated interlock with
manual reset, stop and emergency stop
1)
 Switchable modules see section4.3
When the emergency stop button is pushed, the
PF-O-xDI-SIL switches off the 24V supply for the mod-
ules
1)
within the safety segment and thus also contactors K3
and K4. The failure of a switching element in the emergency
stop button or the safety door contact as well as a cross-cir-
cuit in their supply lines does not result in the failure of the
emergency stop mechanism and is detected within the
fault-reaction time.
A stop is performed by switching off K3 and K4 via the PLC.
The door can be opened when the PLC releases the inter-
lock.
With opening of the safety door a discrepancy er-
ror between S2 and S3 occurs. This error has to
be reset with S1.
The PF-O-xDI-SIL switches on the 24V supply for
modules
1)
within the safety segment if
the emergency stop button is unlocked
and the safety door is closed
and the PLC has activated and engaged the interlock
and the feedback circuit (NC contacts of K3 and K4) is
closed
and the start push button has been pushed and released
again.
Contactors K3 and K4 are controlled by the PLC and can
switch on as soon as the PF-O-xDI-SIL has switched on
the 24V supply.
7.10 Dual-channel safety door monitoring, magnetically operated interlock with manual reset and
emergency stop