In the event of a malfunction occurring on a u-remote sta-
tion, carry out the following recommended measures. If the
malfunction cannot be xed, please send the affected prod-
uct to Weidmüller.
You can nd all Weidmüller addresses and your local con-
tact on the Internet at www.weidmueller.com/countries.
Weidmüller does not assume any liability if the base or
electronic module has been tampered with!
8.1 Safe I/O modules
UR20-4DI-4DO-PN-FSOE, UR20-4DI-4DO-PN-FSOE-V2, UR20-4DI-4DO-PN-FSPS, UR20-4DI-4DO-PN-FSPS-V2
LED Status Recommended action
Status LED Red:
Module has not been snapped properly
Error in the supply voltage
Check that the module has been snapped into place properly
Check supply voltage
Internal error detected Module might have switched off caused by overtemperature; check the
temperature inside the switch cabinet
If the error has not been xed, send the module to Weidmüller for a technical
examination.
Safety address is not set properly Check the safety address (e.g. via the web server)
If no address is displayed in the web server set the safety address again
as described in section 3.5
Communication failure Check wiring
Restart the coupler
Flashes alternating red and green
3s green / 1s red: Module is waiting for parameters from the safety
control (e.g. after the power up) or safety address is not set according
to the project plan
1s green / 1s red: Error pending
Intervention via the safety control is needed
Set the correct safety address
Check the parameter check sum in the project planning
Status must be acknowledged via the safety control
1.1 / 1.4
2.1 / 2.4
Yellow: Input 0 / 1 active
Yellow: Input 2 / 3 active
1.3
2.3
Red: Error input 0 / 1
Red: Error input 2 / 3
At least one AUX-O is overloaded or short circuit with the supply voltage
Readback error on the test pulses of at least one input (e.g. caused by
external short circuit)
The parameterised discrepancy time of this pair of inputs has been
exceeded
Check wiring
Check parameterisation
If the error has not been xed, send the module to Weidmüller for a technical
examination.
3.1 / 3.3
4.1 / 4.3
Yellow: Output 0 / 1 active
Yellow: Output 2 / 3 active
3.2 / 3.4
4.2 / 4.4
Red: Error output 0 / 1
Red: Error output 2 / 3
Output is overloaded
Short circuit with the supply voltage or ground or cross-fault with
another channel
Minimum load has been underrun (e.g. after wire break)
Readback error
Check wiring
Check whether the load circuit is interrupted
If the error has not been xed, send the module to Weidmüller for a technical
examination.