User Documentation

ANNEX
A-2 1484600000/07/11.2020u-remote IP20 modules for functional safety manual
Equipment type / equipment ID
Version: HW/FW Date:
Reviewer 1: Reviewer 2:
Notes:
No. Requirement (mandatory) yes Remark
1 The corresponding manuals were consulted during planning
(“u-remote Manual “ and “Modules for functional safety manual”).
2 The sensors/control devices are approved for connection to the re-
spective module.
3 The power supply was planned as per the safety extra-low voltage
guidelines in accordance with PELV or SELV.
4 The module was externally fused according to the guidelines in the
“Modules for functional safety manual”.
5 Measures to prevent simple manipulations have been planned.
6 Measures against plug mix-ups have been planned.
7 The requirements for the sensors and installation of cables cor-
respond to the applicable safety standards (SIL, Cat., PL) and the
planned implementation takes these standards into consideration.
8 The guidelines for per-channel conguration have been dened.
9 The intentional starting up of potentially hazardous processes is
only possible while looking into the danger zone at the same time.
10 If the installation requires exclusions of faults: the measures have
been realized.
11 The planned use corresponds to the intended use.
12 The environmental conditions meet the guidelines that are speci-
ed in the technical data.
Requirement (optional) yes/no Remark
13 The accessories to be used were selected according to the order
data in the “Modules for functional safety manual”.
14 The guidelines for installation and electrical set-up were dened
and handed over to the departments performing the work.
15 The guidelines for commissioning were dened and handed over to
the departments performing the work.
Date / Signature of Reviewer 1: Date / Signature of Reviewer 2:
Checklist for the use of u-remote safety modules
Sheet 1/3: Planning