u-remote Setting PROFIsafe on Siemens PLC with TIA Portal Commissioning instructions
Setting PROFIsafe on Siemens PLC with TIA Portal Revisions Version Date Changes 01 05.2016 First edition Contact Weidmüller Interface GmbH & Co. KG Klingenbergstraße 16 32758 Detmold, Germany T +49 5231 14-0 F +49 5231 14-292083 info@weidmueller.com www.weidmueller.com xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Contents 1. In s tall th e Weid m ülle r CP D - To o l 4 2. Cre a tin g a n ew pro je c t in S iem e n s TIA-P o rta l 5 3. In te g ratio n o f UR20-4DI-4DO-P N-FS P S a n d 10 3.1 3.2 3.3 UR20-8DI-P N-FS P S o n P ROFINET Install a GSDML file Add a UR20 safety module to the UR20 IO device PROFIsafe parameter settings 4. Exa m p le s of wirin g a nd p a ra m ete r s e ttin g s o f s o m e 20 s a fe ty d e vic e s to u -re m o te 5.
Setting PROFIsafe on Siemens PLC with TIA Portal 1. Install the Weidmüller CPD – Tool Th e We id m ülle r CP D – To o l is a n e m b e d d e d pro g ra m for the c alc u latio n o f th e c h e c k s u m in S TEP 7 o r TIA P o rta l d e p e n d in g o n th e pa ra m ete r s e t for th e m o d ule UR20-4DI-4DO-P N-FS PS o r UR20-8DI-P N-FS PS 1) Unzip the file “Setup_xx.zip” 2) Start the program “setup.exe” and wait until the installation is finished xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal 2. Creating a new project in Siemens TIA-Portal Start TIA Portal from the desktop 1) Double click the symbol like this 2) After TIA has opened, switch to the “Portal view” if necessary xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Create a new project 4. 2. 3. xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Add new device xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Choose the CPU xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Save your Project xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal 3. Integration of UR20-4DI-4DO-PN-FSPS and UR20-8DIPN-FSPS on PROFINET Insert a PROFINET net work 1) Expand the tree “PROFINET interface [X2]” 2) Choose the IP address 3) Add new subnet 1 2 3 xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Advanced PROFINET settings 1) Open/Choose the folder “Net view” 2) Choose and expand Advanced options 3) Make further settings here 1 2 3 xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Install a GSDML file 1) Open “Options and click “install general station description file (GSD) 2) Open the path and choose the GSDML file to install 3) Push the button “install”. The files will installed 1 2 3 xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Install a GSDML file 1) To reopen the view “Devices & Networks” double click the line 1 xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Insert UR20 to the PROFINET line. 1) Expand the branch “Other field devices” and place UR20 by drag and drop 1 xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Further settings for UR20 PROFINET IO device. 1) Double click the symbol of UR20 2) Connect UR20 to the network PROFINET by choosing the subnet 3) Change the name of UR20 to a unique name according to the PROFINET requirements 1 2 3 xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Connect UR20 PN IO device into the PLC PN IO controller system 1) Mark and right mouse click “Not assigned” 2) Select the IO controller 1 xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal UR20 PN IO device is connected into the PLC PN IO controller system xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Add a UR20 safety module to the UR20 IO device 1) Change to the folder “Device view” 2) Choose a module e.g. “UR-4DI-4DO-PN-FSPS and place the module by drag and drop 1 2 xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal PROFIsafe parameter settings 1) Set the Source F-Address (F-CPU) 2) Set the F-Address of the module with the DIP switches NOTE: Each address change needs first an address set to “0” and power up the module. Then set the new address and power up the module again. 3) Set the Destination F-Address (I/O Device or DP-Slave e.
Setting PROFIsafe on Siemens PLC with TIA Portal 4. Examples of wiring and parameter settings of some safety devices to u-remote Connecting an emergency STOP button • Wire the safety light curtain as shown below (e.g. CH2 and CH3) • For this using the test pulses have to be disabled Further information you will find in the u-remote safety manual. xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal PROFIsafe parameter settings of the UR20 module 1) The parameter is adjusted to “dual channel” 2) Start the device Tool by mark the module and right mouse click 2 1 xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Calculate the check sum 1) Confirm each parameter 2) Click the button “CRC calculate” to get the CRC value 3) Mark and copy the CRC value 4) Close the program 1 2 3 xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Adjust the CRC value of the UR20 module 1) Click on “PROFIsafe”. It will open the PROFIsafe settings of the module 2) Paste the CRC value into “F_iPar_CRC” 3) Download the configuration into the PLC 3 1 2 xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal 5. Integration of UR20-4DI-4DO-PN-FSPS and UR20-8DIPN-FSPS on PROFIBUS Insert a PROFIBUS net work 1) Expand the tree “MPI/DP interface [X1]” 2) Add a new subnet and make further settings for PROFIBUS 1 2 xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Install a GSD file 1) Open “Options and click “install general station description file (GSD) 2) Open the path and choose the GSD file to install 3) Push the button “install”. The files will be installed 1 2 3 xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Reopen Devices and networks 1) To reopen the view “Devices & Networks” double click the line 1 xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Insert UR20 to the PROFIBUS line 1) Expand the branch “Other field devices” and place UR20 by drag and drop 1 xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Further settings for UR20 PROFIBUS DP slave. 1) Double click the symbol of UR20 2) Connect UR20 to the network PROFINET by choose the subnet 3) Change the DP address of UR20 according to the rotary switches of the UR20 coupler 1 2 3 xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal Connect UR20 DP slave into the PLC PROFIBUS system 1) Mark and right mouse click “Not assigned” 2) Select the DP master 1 2 xxxxxx0000/01/05.
Setting PROFIsafe on Siemens PLC with TIA Portal UR20 DP slave is connected into the PLC PROFIBUS system xxxxxx0000/01/05.