User Documentation

Setting PROFIsafe on Siemens PLC with TIA Portal
xxxxxx0000/01/05.2016 19
PROFIsafe parameter settings
1) Set the Source F-Address (F-CPU)
2) Set the F-Address of the module with the DIP switches
NOTE: Each address change needs first an address set to “0” and power up the
module. Then set the new address and power up the module again.
3) Set the Destination F-Address (I/O Device or DP-Slave e.g UR20)according to the
DIP switches of the module
4) Set the check sum CRC getting from the CPD Tool (see the next page)
1
2
4
3