User Documentation

4 Module descriptions | Digital input and output modules IP67, PROFIBUS, 60mm, metal housing
212484950000/00/03.2016 Manual UR67-PROIFBUS
Technical data UR67-PB-78-8DIDO-12-60M
(2426380000)
UR67-PB-78-16DI-12-60M
(2426390000)
UR67-PB-78-16DO-12-60M
(2426400000)
Supply electronics/sensors
Rated voltage U
S
24 V DC (SELV/PELV)
Voltage range
24VDC ± 25%
Current consumption electronics
typ. 60mA
Voltage sensors
min. (U
System
- 1.5V)
Current consumption sensors
max. 200mA (at T
u
30°C)
Reverse polarity protection
yes
Supply indicator (U
S
)
LED green/red
Connection
MINI, 7/8" plug and socket, 5-pole
Supply of actuators
Rated voltage U
L
24 V DC (SELV/PELV) 24 V DC (SELV/PELV)
Voltage range
24VDC ± 25% 24VDC ± 25%
Potential isolation
yes yes
Low voltage threshold
typ. 17 V typ. 17 V
Low voltage detection delay
typ. 300ms typ. 300ms
Reverse polarity protection
yes yes
Actuator supply indicator (U
L
)
LED green/red LED green/red
Connection
MINI, 7/8" plug and socket, 5-pole MINI, 7/8" plug and socket, 5-pole
General data
Protection class
IP 67 (only with all sockets closed)
Ambient temperature
-10°C … +60°C
Weight
605 g
Housing material
Zinc diecast
Vibration resistance vibrations
15 g / 5 … 500 Hz
Vibration resistance schock
50 g / 11 ms
Tightening torques
Mounting screw M6
1.0 Nm
Plug-in connector M12
0.6 Nm
1) With inductive loads of utilisation category DC13 (acc.EN60947-5-1) the outputs can switch currents of 0.5A with a frequency of 1Hz.
2) Technically feasible and allowed under the following conditions: looped through sensor/system supply max. 2.5 A; minimal cross section of the power supply
cable 5 x 1.0 mm²; ambient temperature max. 40°C (104°F)