User Documentation

In case the Properties PROFIBUS interface window
will not open automatically please click on “Properties”.
Properties PROFIBUS interface MPI/DP
Click on New.
Enter a name for the subnet.
Confirm three times by clicking OK.
A network line which has the subnet name is now displayed
in the conguration window.
PROFIBUS configuration
Linking a module
Click on the network line in the configuration window.
In the device catalogue under PROFIBUS IO/Additional
field devices/ I/O /UR67 system open the module line
from which you want to add a module (e.g. UR67-PB-78-
XXX-12-60M).
Choosing the module
Double-click on the designated module line or drag it
exactly to the subnet line.
The module line is added to the subnet and the window
Properties PROFIBUS interface” for this module line
opens.
Adjusting the PROFIBUS address
Choose the address which is adjusted on the module
(rotary switches) and confirm with OK.
Each PROFIBUS address must only be set
once!
All settings only take effect once they have
been loaded into the component/control unit
(see below).
7 Commissioning | Commissioning the UR67 module
402484950000/00/03.2016 Manual UR67-PROIFBUS