Brochure/Catalogue

C
C.14 2028840000
Lightning and surge protection
for low voltage supply
Type I and II lightning arrester
No-leakage-current version suitable for use upstream of
the electrical meter
Pluggable arrester
Suitable with 25 kA (10/350 µs) for protective level I, II,
III and IV (LPL I/II/III/IV)
Tested according to IEC 61643-11 for Type I and II surge
protection
Can also be used as Type II surge protection
Technical data
Rated voltage (AC)
Max. continuous voltage, Uc (AC)
Max. continuous voltage, Uc (N-PE)
Lightning test current Iimp (10/350 µs) [L-PE]
Lightning test current Iimp (10/350 µs) [N-PE]
Discharge current I
n
(8/20µs) wire-PE
Discharge current I
n
(8/20µs) GND-PE
Discharge current I
max
(8/20µs) wire-PE
Discharge current I
max
(8/20µs) GND-PE
Requirements class, acc. to EN 61643-11
Short-circuit current rating I
SCCR
Leakage current at U
n
Rated load current I
L
Fuse
Temporary surge voltage (over-voltage) - TOV
Protection level with I
N
(L/N-PE)
Protection level with I
N
(N-PE)
Response time
Optical function display
Design
Colour
Ambient temperature (operational)
Storage temperature
Connection according to IEC 947-7-1
Solid
Stranded
Stripping length
Tightening torque
Approvals
Approvals
Standards
Dimensions / Signalling contact info
Clamping range (nominal / min. / max.) mm²
Height x width x depth mm
Signalling contact
Note
Ordering data
without remote signalling contact
with remote signalling contact (R)
Note
Accessories
Note
VPU I 3+1/R LCF 280 V / 25 kA
TN-S, TT
2. 2.
&+$1*(
8
&+$1*(
8
2.
&+$1*(
1
1
8
230 V
280 V
260 V
25 kA
100 kA
25 kA
100 kA
100 kA
100 kA
T1, T2
25 kA
30 µA
100 A
250 A gL (if mains > 250 A)
438 V
≤ 1.6 kV
≤ 1.6 kV
≤ 100 ns
green = OK; red = arrester is defective - replace
Installation housing; 8 TE, Insta IP 20
Black, Arrester red / blue
-40 °C...70 °C
-40 °C...80 °C
4...16 mm²
2.5...50 mm²
15 mm
2...3 Nm
CE; EAC; OEVE
IEC61643-11, EN61643-11
no remote sig. contact with remote signalling (R)
16 / 4 16 / 4
94 / 142.4 / 69 106 / 142.4 / 69
No 250 V 1A 1CO
Type Qty. Order No.
VPU I 3+1 LCF 280V/25KA 1 1351780000
VPU I 3+1 R LCF 280V/25KA 1 1351770000
Pluggable spare arrester L-N VPU I 0 LCF 280 V/25 kA-1351540000;
N-PE VPUI 0 N-PE 260 V/100 kA-1351940000
VPU I 1+1/R LCF 280 V / 25 kA
1-phase
8
2.
&+$1*(
230 V
280 V
260 V
25 kA
100 kA
25 kA
100 kA
100 kA
100 kA
T1, T2
25 kA
30 µA
100 A
250 A gL (if mains > 250 A)
438 V
≤ 1.6 kV
≤ 1.6 kV
≤ 100 ns
green = OK; red = arrester is defective - replace
Installation housing; 4TE, Insta IP 20
Black, Arrester red / blue
-40 °C...70 °C
-40 °C...80 °C
4...16 mm²
2.5...50 mm²
15 mm
2...3 Nm
CE; EAC; OEVE
IEC61643-11, EN61643-11
no remote sig. contact with remote signalling (R)
16 / 4 16 / 4
94 / 71.2 / 69 106 / 71.2 / 69
No 250 V 1A 1CO
Type Qty. Order No.
VPU I 1+1 LCF 280V/25KA 1 1351750000
VPU I 1+1 R LCF 280V/25KA 1 1351740000
Pluggable spare arrester L-N VPU I 0 LCF 280 V/25 kA-1351540000;
N-PE VPUI 0 N-PE 260 V/100 kA-1351940000
Type I and II lightning arrester