Lightning and surge protection
for control and instrumentation signals
VSSC 4 CL FG EX - protection for floating earth,
intrinsically safe current loops
UNPROTECTED PROTECTED
1
TS
2
3
4
Dielectric strength at FG against PE ≥ 500 V
Volume resistance 1.8
Ω 10 %
Overload - failure mode Modus 2
Requirements category acc. to IEC 61643-21 C2, C3, D1
Surge current-carrying capacity C1
Surge current-carrying capacity C2 2.5 kA 8/20 µs 5 kV 1.2/50 µs
Surge current-carrying capacity C3 50 A 10/1000 μs
Surge current-carrying capacity D1 0.5 kA 10/350 μs
Discharge current I
n
(8/20 µs) wire-wire/wire-PE/GND-PE 2.5 kA / 2.5 kA
Discharge I
max
(8/20 μs) wire-wire/wire-PE/GND-PE 5 kA / 5 kA
Lightning test I
imp
(10/350 µs) wire-wire/wire-PE/GND-PE / 0.5 kA
Type of connection Screw connection, Torx
®
T15, Slotted 0.8 x 4
Storage temperature -40 °C...80 °C
Ambient temperature (operational) -40 °C...70 °C
Protection degree IP20
UL 94 flammability rating V-0
Connection data
Type of connection Screw connection, Torx
®
T15, Slotted 0.8 x 4
Tightening torque 0.5 Nm
Wire connection cross section, finely stranded, max. 4 mm²
Wire connection cross-section, finely stranded, min. 0.5 mm²
Wire cross-section, solid, max. 6 mm²
Wire cross-section, solid, min. 0.5 mm²
Wire cross-section, stranded, max. 4 mm²
Wire cross-section, stranded, min. 0.5 mm²
Stripping length 10 mm
Mounting rail TS 35
Approvals
Approvals CE; CSAEX; DEKRAATEX; EAC; GOSTEX; IECEXDEK; TUEV
Standards IEC61643-21:2009, DIN EN 60079-0.2009, DIN EN 60079-
26:2007, DIN EN 61241-11:2006
ATEX - dust labelling II 1 D Ex ia IIIC T135 °C …T85 °C Da
ATEX - gas labelling II 1 G Ex ia IIC T4… T6 Ga
IECEx - dust labelling II 1 D Ex ia IIIC T135 °C …T85 °C Da
IECEx - gas labelling II 1 G Ex ia IIC T4… T6 Ga
Note
Dimensions Dimensions
Height x width x depth mm 76 / 12.2 / 58.5
ATEX approval: II 1 G EX ia IIC T4...T6 Ga II 1 D EX ia IIIC T135°C...T85°C
DEKRA No: 11ATEX0023 X
Technical data
2-level surge protection with screw connection for intrinsically safe
instrumentation and control signals
Surge protection in terminal block design
Width of only 12.4mm
Torx
®
slotted screw connection
Version with floating-earth PE connection used to avoid differences in
voltage potential
Can be used in accordance with installation standard IEC 62305 as
well as in ATEX user standards
Integrated PE foot, safely discharges up to 20kA (8/20 μs) and
2.5kA (10/350 μs) to PE
VARITECTOR SSC EX