Brochure/Catalogue

B
B.162 2028840000
Lightning and surge protection
for control and instrumentation signals
VSSC 6 TR FG EX - protection for floating,
intrinsically safe current loops with isolator function
UNPROTECTED PROTECTED
1
TS
2
4
5
3 6
UNPROTECTED PROTECTED
1
TS
2
4
5
3 6
1066490000
1421440000
Dielectric strength at FG against PE ≥ 500 V
Volume resistance 1.8
Ω 10 %
Overload - failure mode Modus 2
Requirements category acc. to IEC 61643-21 C2, C3, D1
Surge current-carrying capacity C1
Surge current-carrying capacity C2 2.5 kA 8/20 µs 5 kV 1.2/50 µs
Surge current-carrying capacity C3 50 A 10/1000 μs
Surge current-carrying capacity D1 0.5 kA 10/350 μs
Discharge current I
n
(8/20 µs) wire-wire/wire-PE/GND-PE 2.5 kA / 2.5 kA
Discharge I
max
(8/20 μs) wire-wire/wire-PE/GND-PE 5 kA / 5 kA
Lightning test I
imp
(10/350 µs) wire-wire/wire-PE/GND-PE / 0.5 kA
Type of connection Screw connection, Torx
®
T15, Slotted 0.8 x 4
Storage temperature -40 °C...80 °C
Ambient temperature (operational) -40 °C...70 °C
Protection degree IP20
UL 94 flammability rating V-0
Connection data
Type of connection Screw connection, Torx
®
T15, Slotted 0.8 x 4
Tightening torque 0.5 Nm
Wire connection cross section, finely stranded, max. 4 mm²
Wire connection cross-section, finely stranded, min. 0.5 mm²
Wire cross-section, solid, max. 6 mm²
Wire cross-section, solid, min. 0.5 mm²
Wire cross-section, stranded, max. 4 mm²
Wire cross-section, stranded, min. 0.5 mm²
Stripping length 10 mm
Mounting rail TS 35
Approvals
Approvals CE; CSAEX; DEKRAATEX; EAC; GOSTEX; IECEXDEK; TUEV
Standards IEC61643-21:2009, DIN EN 60079-0.2009, DIN EN 60079-
26:2007, DIN EN 61241-11:2006
ATEX - dust labelling II 1 D Ex ia IIIC T135 °C …T85 °C Da
ATEX - gas labelling II 1 G Ex ia IIC T4… T6 Ga
IECEx - dust labelling II 1 D Ex ia IIIC T135 °C …T85 °C Da
IECEx - gas labelling II 1 G Ex ia IIC T4… T6 Ga
Note
Dimensions Dimensions
Height x width x depth mm 88.5 / 12.2 / 81
ATEX approval: II 1 G EX ia IIC T4...T6 Ga II 1 D EX ia IIIC T135°C...T85°C
DEKRA No: 11ATEX0023 X
Technical data
2-level surge protection with screw connection for intrinsically safe
instrumentation and control signals
Surge protection in terminal block design
Alignment width of only 12.4 mm
Signals can be separated for measurement
For use in zones 2, 1, and 0
Torx
®
slotted screw connection
Can be used in compliance with installation standard IEC 62305
Tested according to IEC 61643-21: D1, C2, C3
Integrated PE foot, safely discharges up to 20 kA (8/20 μs) and 2.5
kA (10/350 μs) to PE
VARITECTOR SSC EX