Approval/Certificate/Document of Conformity

Certificate: 70000877
Project: 70000877
Master Contract: 200039
Date Issued: March 24, 2014
DQD 507 Rev. 2012-05-22 Page 2
CLASS 2258 04 PROCESS CONTROL EQUIPMENT Intrinsically safe entity-For Hazardous Locations
CLASS 2258 84 PROCESS CONTROL EQUIPMENT Intrinsically safe entity For Hazardous Locations
certified to U.S
IS, Class I Div 1, GP A,B,C,D T4 … T6, Ta = 70 / 85 / 120 °C, Entity
Ex ia IIC T4 … T6, Ta = 70 / 85 / 120 °C
Class I, Zone 1, AEx ia IIC T4 … T6, Ta = 70 / 85 / 120 °C
The Surge Voltage Protection Unit of Series VSSC ... Ex serves to limit any surge voltages in intrinsically safe
circuits. They are intrinsically safe as per Control Drawing 3 57951.
The earth connection can be made via the mounting foot to a normalized metal mounting rail and via a terminal.
Several units for different intrinsically safe circuits may be mounted next to each other.
Ambient temperature range: -40 °C to +120 °C for temperature class T4,
-40 °C to +85 °C for temperature class T5,
-50 °C to +70 °C for temperature class T6.
Electrical data as per Control Drawing 3 57951.
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 157-92 (R2012)
Intrinsically Safe and Non-Incendive Equipment for Use in
Hazardous Locations
CSA Std C22.2 No. 213-M1987
Non-Incendive Electrical Equipment for Use in Class I, Division 2
Hazardous Locations
ANSI/UL Standard 913 (2006)
Intrinsically Safe Apparatus and Associated Apparatus for Use in
Class I, II, and III, Division 1, Hazardous (Classified) Locations
ISA12.12.01_2013
Nonincendive Electrical Equipment for Use in Class I and II,
Division 2 and Class III, Divisions 1 and 2 Hazardous (Classified)
Locations
CAN/CSA-C22.2 No. 60079-0-11
ANSI/ISA-60079-0 (2009)
Electrical Apparatus for Explosive Gas Atmospheres - Part 0:
General Requirements
CAN/CSA-E60079-11-11
ANSI/ISA-60079-11(2007) ;
Electrical apparatus for explosive gas atmospheres; Part 11:
Intrinsic Safety “i”
CAN/CSA E60079-15-12
ANSI/ISA-60079-15 (12.12.02)-2009
Electrical Apparatus for explosive gas atmospheres - Part 15:
Type of protection “n”
C22.2 No. 142-M1987 (R2004)
Process Control Equipment
UL916-2007
Energy Management Equipment