Brochure/Catalogue

C
C.24 2028840000
Lightning and surge protection
for low voltage supply
Type I and II lightning arrester for use
downstream of the electrical meter
Suitable for protective level III and IV (LPL III/IV)
Pluggable arresters
Tested according to IEC 61643-11 for Type I and II
lightning and surge protection
Can also be used as Type II surge protection
Technical data
Rated voltage (AC)
Max. continuous voltage, Uc (AC)
Lightning test current Iimp (10/350 µs) [L-PE]
Discharge current I
n
(8/20µs) wire-PE
Discharge current I
max
(8/20µs) wire-PE
Requirements class, acc. to EN 61643-11
Short-circuit current rating I
SCCR
Leakage current at U
n
Rated load current I
L
Fuse
Temporary surge voltage (over-voltage) - TOV
Protection level with I
N
(L/N-PE)
Response time
Optical function display
Design
Colour
Ambient temperature (operational)
Storage temperature
Connection according to IEC 947-7-1
Solid
Stranded
Stripping length
Tightening torque
Approvals
Approvals
Standards
Dimensions / Signalling contact info
Clamping range (nominal / min. / max.) mm²
Height x width x depth mm
Signalling contact
Note
Ordering data
without remote signalling contact
with remote signalling contact (R)
Note
Accessories
Note
VPU I 4/R 280 V / 12.5 kA
TN-S
U U
OK
CHANGE
OK
CHANGE
U
OK
CHANGE
U
OK
CHANGE
11 1412
PE
230 V
280 V
12.5 kA
20 kA
50 kA
T1, T2
25 kA
100 µA
250 A gL (if mains > 250 A)
438 V
≤ 1.4 kV
≤ 25 ns
green = OK; red = arrester is defective - replace
Installation housing; 4TE, Insta IP 20
Black, Arrester red
-40 °C...70 °C
-40 °C...80 °C
4...16 mm²
2.5...50 mm²
15 mm
2...3 Nm
CE; EAC; OEVE
IEC61643-11, EN61643-11
no remote sig. contact with remote signalling (R)
16 / 4 16 / 4
94 / 71.2 / 69 106 / 71.2 / 69
No 250 V 1A 1CO
Type Qty. Order No.
VPU I 4 280V/12,5KA 1 1352180000
VPU I 4 R 280V/12,5KA 1 1352190000
Pluggable spare arrester VPU I 0 280 V/12.5 kA-1352120000
VPU I 3/R 280 V / 12.5 kA
TN-C
PE (N)
U
OK
CHANGE
U
OK
CHANGE
U
OK
CHANGE
11 1412
PE (N)
230 V
280 V
12.5 kA
20 kA
50 kA
T1, T2
25 kA
100 µA
250 A gL (if mains > 250 A)
438 V
≤ 1.4 kV
≤ 25 ns
green = OK; red = arrester is defective - replace
Installation housing; 3TE, Insta IP 20
Black, Arrester red
-40 °C...70 °C
-40 °C...80 °C
4...16 mm²
2.5...50 mm²
15 mm
2...3 Nm
CE; EAC; OEVE
IEC61643-11, EN61643-11
no remote sig. contact with remote signalling (R)
16 / 4 16 / 4
94 / 53.4 / 69 106 / 53.4 / 69
No 250 V 1A 1CO
Type Qty. Order No.
VPU I 3 280V/12,5KA 1 1352200000
VPU I 3 R 280V/12,5KA 1 1352220000
Pluggable spare arrester VPU I 0 280 V/12.5 kA-1352120000
Type I and II lightning arrester