Lightning and surge protection
for low voltage supply
Type I and II lightning arrester for use in photo-
voltaic applications
Suitable for protection level III and IV (LPL III/IV)
Can also be used as TypeII surge protection
Tested in accordance with EN 50539-11
Suitable for use in accordance with IEC 60364-7-712/
EN 50539-12
Use if the separation distance cannot be observed
Technical data
Max. continuous voltage, Uc (DC)
Lightning test current I
imp
(10/350 µs) [L-PE]
Discharge current I
max
(8/20µs) wire-PE
Discharge current I
n
(8/20µs) wire-PE
PV voltage, acc. to IEC 60364-7-712
Leakage current at U
n
Response time
Optical function display
Design
Colour
Ambient temperature (operational)
Storage temperature
Connection according to IEC 947-7-1
Solid
Stranded
Stripping length
Tightening torque
Technical data - photovoltaic
Maximum continuous operating voltage UCPV mode +/-, -/PE, +/PE
Protection level U
p
mode (+/-)
Protection level U
p
mode(+/PE)
Protection level U
p
mode (-/PE)
Conditions and requirements
Short-circuit resistance I
SCPV
PV system voltage, max. U
cpv
Approvals
Approvals
Standards
Dimensions / Signalling contact info
Clamping range (nominal / min. / max.) mm²
Height x width x depth mm
Signalling contact
Note
Ordering data
without remote signalling contact
with remote signalling contact (R)
Note
Accessories
Note
VPU I 2+0 PV 600 V
Photovoltaics
8 8
2.
&+$1*(
2.
&+$1*(
600 V
12.5 kA
40 kA
40 kA
< 600 V
30 µA
≤ 25 ns
green = OK; red = arrester is defective - replace
Installation housing; 4TE, Insta IP 20
Black
-40 °C...70 °C
-40 °C...80 °C
4...16 mm²
2.5...50 mm²
15 mm
2...3 Nm
600 V DC
≤ 3.6 kV
≤ 1.8 kV
≤ 1.8 kV
EN 50539-11
200 A
600 V
CE; EAC
EN 50539-11
no remote sig. contact with remote signalling (R)
16 / 4 16 / 4
94 / 71.2 / 69 106 / 71.2 / 69
No 250 V 1A 1CO
Type Qty. Order No.
VPU I 2+0 PV 600V DC 1 1351520000
VPU I 2+0 R PV 600V DC 1 1351490000
*UNDEFINED TEXT*
VPU I 2+0 PV 1000 V
Photovoltaics
8 8
2.
&+$1*(
2.
&+$1*(
1000 V
12.5 kA
40 kA
40 kA
≤ 1000 V
30 µA
≤ 25 ns
green = OK; red = arrester is defective - replace
Installation housing; 4TE, Insta IP 20
Black
-40 °C...70 °C
-40 °C...80 °C
4...16 mm²
2.5...50 mm²
15 mm
2...3 Nm
1000 V DC
≤ 5.2 kV
≤ 2.6 kV
≤ 2.6 kV
EN 50539-11
200 A
1000 V
CE; EAC
EN 50539-11
no remote sig. contact with remote signalling (R)
16 / 4 16 / 4
94 / 71.2 / 69 106 / 71.2 / 69
No 250 V 1A 1CO
Type Qty. Order No.
VPU I 2+0 PV 1000V DC 1 1351470000
VPU I 2+0 R PV 1000V DC 1 1351430000
Lightning and surge protection for photovoltaic systems on the DC side