Lightning and surge protection
for low voltage supply
Type I and II lightning arresters
Suitable with 25kA (10/350 µs) for protective level I, II,
III and IV (LPL I/II/III/IV)
Pluggable arrester
Tested according to IEC 61643-11 for Type I and II surge
protection
Can also be used as Type II surge protection
Field of application downstream of the main electrical
meter
Technical data
Rated voltage (AC)
Max. continuous voltage, Uc (AC)
Lightning test current Iimp (10/350 µs) [L-PE]
Discharge current I
n
(8/20µs) wire-PE
Discharge current I
max
(8/20µs) wire-PE
Requirements class, acc. to EN 61643-11
Short-circuit current rating I
SCCR
Leakage current at U
n
Rated load current I
L
Fuse
Temporary surge voltage (over-voltage) - TOV
Protection level with I
N
(L/N-PE)
Response time
Optical function display
Design
Colour
Ambient temperature (operational)
Storage temperature
Connection according to IEC 947-7-1
Solid
Stranded
Stripping length
Tightening torque
Approvals
Approvals
Standards
Dimensions / Signalling contact info
Clamping range (nominal / min. / max.) mm²
Height x width x depth mm
Signalling contact
Note
Ordering data
without remote signalling contact
with remote signalling contact (R)
Note
Accessories
Note
VPU I 4/R 400V / 25kA
TN-S, TN C-S
2. 2.
&+$1*(
8
&+$1*(
8
2.
&+$1*(
3(
8
2.
&+$1*(
3(
8
400 V
400 V
25 kA
25 kA
100 kA
T1, T2
25 kA
30 µA
100 A
250 A gL (if mains > 250 A)
620 V
≤ 1.9 kV
≤ 25 ns
green = OK; red = arrester is defective - replace
Installation housing; 8 TE, Insta IP 20
Black, Arrester red
-40 °C...70 °C
-40 °C...80 °C
4...16 mm²
2.5...50 mm²
15 mm
2...3 Nm
EAC
IEC61643-11, EN61643-11
no remote sig. contact with remote signalling (R)
16 / 4 16 / 4
106 / 142.4 / 69 106 / 142.4 / 69
No 250 V 1A 1CO
Type Qty. Order No.
VPU I 4 400V/25KA 1 1438010000
VPU I 4 R 400V/25KA 1 1438020000
Replacement arrester VPU I 0 400 V/25 kA-1351790000 for plug-in
Type I and II lightning arrester